blown fuse caused by module failure due to transient over-stress (a condition which causes
the Fault Indication). It also transmits the occurrence to a remote indicator (an accessory item)
via an optically isolated Class II wire pair.
Beep Disable Switch: When a fault has been indicated and noted by authorized personnel,
the audible beep tone may be disabled by momentarily pressing the beep disable switch. The
Red warning LED will continue to flash. When the malfunctioning fuse and module have been
replaced, the beep disable switch should be pressed again in order to re-enable the audible
beep tone.
Battery Function: In the unlikely event that more than one fuse has blown, a 9-volt alkaline
battery is utilized to power the diagnostic circuitry so as to alert the user that there is a
problem. When this occurs, the flashing Red warning LED, audible beep tone, and remote
transmitter are activated. When multiple Green module LEDs are OFF, it is probable that the
unit’s diagnostic circuitry is being powered from the battery. In order to conserve battery life,
it is recommended that the user press the beep disable switch to turn OFF the audible beep.
After the fuses and modules are replaced, the Red flashing LED will turn OFF. Press the beep
disable switch in order to reactivate the audible warning tone.
Battery Disable: The unit is shipped with the battery disable switch in the disable position
so the battery will not continually discharge in the absence of AC power. When AC power is
first applied, the Red battery-disable LED and Yellow low-battery LED will be lit. The battery
disable switch should be pressed momentarily to enable the battery. This will be indicated by
both the battery disable and low battery LEDs turning OFF.
Low Battery Indication: An illuminated Yellow LED indicates an abnormally low battery
condition. This may be due to low battery voltage or a missing battery. When this happens
the Red warning LED will flash, the audible beep will sound, and the remote indicator will be
enabled. When the user is alerted to the warning status, the illuminated condition of the Yellow
LED and the lighted condition of all the Green module LEDs denotes a battery fault and not
a SPD module power or fuse fault. The Disable Battery switch should then be pressed to
silence the audible alarm beep, flashing LED, and remote warning for the battery malfunction.
The Yellow LED may remain illuminated as a reminder that the battery needs replacing. This
action re-enables the warning function to continue to monitor SPD faults. When the battery is
replaced, the Disable Battery switch should be momentarily pressed. A fresh battery, when the
disable battery switch is pressed, will cause the Yellow LED to turn OFF and will re-enable the
Low Battery warning function after pressing the battery disable switch.
Battery Replacement: Press battery holder and slide battery out. Be sure to follow the battery
polarity marking on the battery compartment.
Test Switch: A “Press to Test Switch” enables the user to test for proper operation of all the
functions described above. When the test switch is held down, the following functions will
occur:
• The Yellow low battery LED will illuminate.
• The Red warning LED will flash.
• The audible tone beeper will sound.
• The Remote Supervisor Panel warning indicator (an accessory item), if wired in, will be
activated, thus also testing the Remote Supervisor Panel.
LIMITED LIFETIME WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use during the lifetime of the product. Leviton’s only obligation
is to correct such defects by repair or replacement, at its option, if the product is returned prepaid, with proof of purchase date, and a description of the problem to
Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y.
11747. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not
used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose. Leviton is not liable for incidental, indirect, special, or consequential
damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) - 1 800 405-5320 (Canada Only) - www.leviton.com
PK-93014-10-00-0A
© 2013 Leviton Mfg. Co., Inc.
G
L1
L3
N
L2
CB
CB
CB
Black
Black
Black
Green
White
G
N
Integrated
Disconnect
FIGURE 1 - 120/208V WYE or
277/480V WYE, Three Phase
4 Wire with Ground
Table 1 - Diagnostic Indicator Functions:
List of the diagnostic functions of the 52000 series panels
Beeper
("Audio Alarm")
Battery Disable
("Low Battery")
Self Test
("Test")
Fault
LED
(Red)
Beeper Remote Module
LEDs
(Green)
Battery
Status
LED
(Yellow)
Disable
Button
Disable
LED
Disable
Button
Disable
LED
Momentary
Action
Button
Mode
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OUT
IN
OFF
ON
OUT
OUT
OFF
OFF
OUT
OUT
Normal
ON
ON
ON
OFF
ON
ON
one or more
OFF
OFF
OFF
OUT
IN
OFF
ON
OUT
OUT
OFF
OFF
OUT
OUT
Module
Fault
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
OUT
OUT
OFF
OFF
OUT
IN
OFF
ON
OUT
OUT
Low
Battery
ON
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OUT
IN
OUT
OFF
OFF
OFF
OUT
OUT
IN
OFF
OFF
OFF
OUT
OUT
OUT
No AC
Power
ON
ON
ON
ON
ON
OUT
OFF
OUT
OFF
IN
Self
Test
FOR CANADA ONLY:
For warranty information and/or product returns, residents of Canada should contact
Leviton in writing at Leviton Manufacturing of Canada Ltd to the attention of the Quality
Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by
telephone at 1 800 405-5320.
CAUTION:
TURN SWITCH
TO OFF
POSITION
TO OPEN
THE DOOR.
0.20 in. - 0.31 in.
(5-8 mm)
ON
OFF
O
ON
OFF
O
CAUTION:
TURN SWITCH
TO OFF
POSITION
TO OPEN
THE DOOR.
FIGURE 2 - Integral disconnect
switch with lockout.
NOTE: Pull red lockout tab out with switch