Network ID number.

Since the Luma-Net

®

 System is a digital network, all panels and devices attached  

(except dimmers) must have a unique network ID number.

If two panels have the same network ID number, the entire network will stop 

functioning.

Panels without a dipswitch must follow this procedure otherwise simply set the dipswitch as 

per the chart on the following page.

To set Network ID number (units without dipswitch):

1.

 Make sure that the 400CP is in the program mode as discussed.

2.

  Press the zone 1,2,3,4 increase buttons at the same time and the BUSY LED will stop 

flashing

3.

  Look up the necessary sequence of 1’s and 0’ for the ID number on the chart at the end of 

this section.

4.

 Using the two buttons indicated below, enter the eight number sequence of 1’s and 0’s.

5.

  The unit will exit this program mode at the release of the eighth press, and the BUSY LED 

will start flashing again.

 ZONE 1                  ZONE 2                    ZONE 3                 ZONE 4

PWR    

 

          BUSY

LUMA-NET

INCREASE

MEMORY LIGHTING CONTROLLER

DECREASE

400  CP

 

    0 

       1

NETWORK ID MODE

WEB 

VERSION

Содержание 400CP

Страница 1: ...400CP Remote Control Panel Installation Operation Guide WEB VERSION ...

Страница 2: ...INTRODUCTION 3 IMPORTANT 3 WIRING 3 PROGRAMMING 5 OPERATION 12 Table of Contents WEB VERSION ...

Страница 3: ...icitly designed for interfacing with it Communication between the 400CP and the dimming system is via a 4 wire interface Three wires carry the RS 422 485 bi directional data A fourth wire carries the DC voltage necessary for powering the unit Wiring cable between the 400CP and the dimming system is class 2 and should be at least 22 AWG 4 conductor shielded twisted pairs BELDEN 8302 8723 22 AWG The...

Страница 4: ...R LED comes on indicating power to the panel The BUSY LED should come on momentarily and then go out and stay out This indicates a successful reconfiguration of the network If the BUSY LED flashes slowly this indicates a duplicate ID number or wiring problem Program the ID number if not already and observe the BUSY LED Note the busy LED also flashes quickly when the program jumper is removed Now test...

Страница 5: ...mper block and disconnect plug in terminal block 2 Hold down all ZONE 1 4 LOWER buttons while connecting terminal block Full Memory Clear Normally the 400CP will not require memory clearing Once the memory is cleared all parameters including fade rate must be reprogrammed Unless it is necessary to clear memory to remove a large or unknown programming skip these steps 1 Remove program jumper block ...

Страница 6: ...quit flashing 3 Press button representing desired number of dimmers as shown in the diagram 4 If more than 256 dimmers are required then press a second button so that the sum of the values of the two buttons pressed will equal the desired number of dimmers 5 The unit will exit this programming mode and the BUSY LED will start flashing again on release of the second press or after a few seconds if on...

Страница 7: ...e to be programmed At this point all currently assigned dimmers will come on The current dimmer selector will be set to one 4 Use the buttons marked as UP and DOWN in diagram to increment or decrement the dimmer channel selector Tap the buttons the required number of times to reach the dimmer channel to be assigned 5 Use the ADD and DELETE buttons to add or delete this dimmer from the zone The lam...

Страница 8: ...d If the factory default setting of 5 seconds is desired for each zone then this step may be ignored To program zone fade time 1 Make sure that the 400CP is in the program select mode as discussed 2 Press the zone 3 increase button to enter fade time mode and the BUSY LED will stop flashing 3 Select the desired zone by pressing the associated button as shown in the diagram 4 Press button marked wit...

Страница 9: ...umber 1 Make sure that the 400CP is in the program mode as discussed 2 Press the zone 4 increase button and the BUSY LED will stop flashing 3 Look up the necessary sequence of 1 s and 0 for the ID number on the chart at the end of this section 4 Using the two buttons indicated below enter the eight number sequence of 1 s and 0 s 5 The unit NOTE All other programming except network ID will have no e...

Страница 10: ...hout dipswitch 1 Make sure that the 400CP is in the program mode as discussed 2 Press the zone 1 2 3 4 increase buttons at the same time and the BUSY LED will stop flashing 3 Look up the necessary sequence of 1 s and 0 for the ID number on the chart at the end of this section 4 Using the two buttons indicated below enter the eight number sequence of 1 s and 0 s 5 The unit will exit this program mod...

Страница 11: ...1011100 60 00111100 61 10111100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78 01110010 79 11110010 80 00001010 81 10001010 82 01001010 83 11001010 84 00101010 85 10101010 86 01101010 87 11101010 88 00011010 89 10011010 90 01011010 91 11011010 92 00111...

Страница 12: ...eviton com or call 1 800 824 3005 This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation This warranty is void if this product is installed improperly or in an improper environment overloaded misused opened abused or altered in any manner or is not used under normal operating conditions or not in accordance with any labels or instructions T...