Page 10
Network ID number.
Since the Luma-Net
®
System is a digital network, all panels and devices attached
(except dimmers) must have a unique network ID number.
If two panels have the same network ID number, the entire network will stop
functioning.
Panels without a dipswitch must follow this procedure otherwise simply set the dipswitch as
per the chart on the following page.
To set Network ID number (units without dipswitch):
1.
Make sure that the 400CP is in the program mode as discussed.
2.
Press the zone 1,2,3,4 increase buttons at the same time and the BUSY LED will stop
flashing
3.
Look up the necessary sequence of 1’s and 0’ for the ID number on the chart at the end of
this section.
4.
Using the two buttons indicated below, enter the eight number sequence of 1’s and 0’s.
5.
The unit will exit this program mode at the release of the eighth press, and the BUSY LED
will start flashing again.
ZONE 1 ZONE 2 ZONE 3 ZONE 4
PWR
BUSY
LUMA-NET
INCREASE
MEMORY LIGHTING CONTROLLER
DECREASE
400 CP
0
1
NETWORK ID MODE
WEB