Smart Process Gating
Leuze electronic GmbH + Co. KG
MLC 530 SPG
25
4.4.1
Operating mode 1 - Qualified stop
The following functions are active in this operating mode (see chapter 8.2 "Operating mode 1"):
• Qualified stop function
• MaxiScan
• Start/restart interlock active (see chapter 5.1 "Start/restart interlock RES")
The following functions can be selected as well:
• SPG timeout extension to up to 100 hours (see chapter 4.5.2 "Gating timeout extension")
• Fixed blanking can be taught with position tolerance of ± 1 beam (see chapter 5.5 "Blanking")
NOTICE
The TH timer hold signal from the control must not be generated by inverting the CS switching
signal.
Operating mode 1 is intended primarily for SPG use at lower conveyor speeds (< 0.1 m/s), e.g., in the auto-
motive sector. For an automatic gating end to be possible at speeds up to 0.1 m/s, t2 is set to 2 s.
With the qualified stop function, a normal stop can be performed without interruption of the protective field
even after the CS switching signal was activated.
TH
CS
PFI
GA
a
t1
t2
t4
t3
CS
Switching signal from the control
TH
Timer hold signal from the control
PFI
Protective field interrupted
GA
Gating active
a
Antivalent signal change between CS and TH
t1
< 4 s
t2
2 s
t3
< 20 s
t4
< 10 min
Fig. 4.2:
Operating mode 1 - Qualified stop