Functions
Leuze electronic GmbH + Co. KG
CML 730i
30
4.7
Power-Up Teach
After applying operating voltage, the “Power-Up Teach” function performs a teach event when the device
is ready for operation.
• If the Power-Up teach is successful, the new teach values are adopted if they are different from the
previously stored teach values.
• If the Power-Up teach is not successful (e.g. object in the light path), the previously saved teach val
-
ues are used.
If the
Auto blanking
function is activated via the receiver control panel, up to four blanking areas
are automatically permitted.
Auto blanking cannot be used to detect transparent objects.
Deactivated beams are lost if the beam mode is changed while auto blanking is active.
NOTICE
Deactivate auto blanking in process mode!
Deactivate auto blanking in process mode.
Activate auto blanking only during commissioning of the device to suppress distracting objects.
NOTICE
Deactivate auto blanking during Power-Up Teach!
Deactivate auto blanking if “Power-Up Teach” is activated (see chapter 4.7).
NOTICE
Resetting all blanking areas!
To deactivate blanking areas, leave auto blanking active with at least the same number of blanking
areas.
Perform a new teach in a free measurement field.
To deactivate blanking with the
Sensor Studio
configuration software, configure the number of blan
-
king areas as zero and, at the same time, deactivate each area.
Perform a new teach.
The “Power-Up Teach” event can only be activated via the receiver control panel.
NOTICE
Deactivate auto blanking during Power-Up Teach!
Deactivate auto blanking if “Power-Up Teach” is activated.
NOTICE
No objects in the light path!
During “Power-Up Teach”, ensure that no beams are partially covered by an object.