www.lesterelectrical.com
4
34748 A
To increase the maximum timer if it has been
decreased from the default value, press and release
the DISPLAY button until Func
1
is displayed.
Continue to hold in the DISPLAY button while you
press and release the START/STOP button. Every
time you press and release the START/STOP
button, the maximum timer will increase by five
minutes. When you are finished increasing the
maximum timer to the desired value, release the
DISPLAY button.
To decrease the maximum timer from 240 minutes,
press and release the DISPLAY button until Func
2
is
displayed. Continue to hold in the DISPLAY button
while you press and release the START/STOP
button. Every time you press and release the
START/STOP button, the maximum timer will
decrease by five minutes. When you are finished
decreasing the maximum timer to the desired value,
release the DISPLAY button.
Changing the shut-off voltage
When the unit is powered up, the shut-off voltage
defaults to its lowest programmable value of 63 volts
(1.75 volts per cell).
To increase the shut-off voltage from the default
setting, press and release the DISPLAY button until
Func3 is displayed. Continue to hold in the
DISPLAY button while you press and release the
START/STOP button. Every time you press and
release the START/STOP button, the shut-off
voltage will increase by 0.1 volts. When you are
finished increasing the shut-off voltage to the
desired value, release the DISPLAY button.
To decrease the shut-off voltage if it has been
increased from the default setting, press and release
the DISPLAY button until Func4 is displayed.
Continue to hold in the DISPLAY button while you
press and release the START/STOP button. Every
time you press and release the START/STOP
button, the shut-off voltage will decrease by 0.1
volts. When you are finished decreasing the shut-off
voltage to the desired value, release the DISPLAY
button.
Changing the discharge data printout interval
Connect a terminal or computer to the nine pin D-
subminiature connector on the discharge unit. The
terminal format is set up to transmit at 1200 baud
with 8 bits, 1 stop bit, and no parity. The default
print routine for the discharge unit is to print data in
one minute intervals but only when the unit is on.
This can be changed to print data once a second by
pressing and releasing the DISPLAY button until
Func5 is displayed. Continue to hold in the
DISPLAY button while you press and release the
START/STOP button. This changes the value
displayed from 60 to a one. If you wish to change
the print routine back to the default setting, press
and release the DISPLAY button until Func5 is
displayed. Continue to hold in the DISPLAY button
while you press and release the START/STOP
button. This changes the value displayed from one
back to a 60.
The display format for the discharge data is the
following:
aaaaa bbbbb ccccc ddddd
where aaaaa = discharge time in minutes
bbbbb = discharge time in seconds
ccccc = present battery voltage
ddddd = lowest battery voltage during
discharge