PS 1 – LCD
www.lesa.de
– the fastest way to get in touch!
8
4.0 Settings menu
4.1
The following chart shows different options for settings. The option will appear in the upper line of
the display while the lower line will show the value to be changed.
1. line of Display
Option for Setting
Explanation
Last Failure
Delete value
The last malfunction will be saved even in case of power-
disconnection and can be deleted by pushing the button
“Quittung”
Level Start
0 – 100 (200) cm
The value determines start level of pump
Level Stop
0 – 100 (200) cm
The value determines stop level of pump
High-water level
0 – 100 (200) cm
Once predetermined value is exceeded, the collective fault report
relay and the high-water relay are activated
Operating limit
0 – 60 Min.
The value 0 deactivates this function. If the value is set between 1-
60 min. the pump shuts off if the set operating time has been
exceeded without interruption
Start Delay
0 – 900 sec.
After a power outage the pump will only start after the pre-set
time is over.The display will show the remaining time.
Stop Delay
0 – 180 sec.
After the Stop level is reached, the pump will keep running until
the pre-set time is over.
Current Limit
0.3 – 16.0 A
If the pump exceeds the set power intake for a certain time, it
shuts off.The display shows: Overload. The pump will only be re-
activated after the button
“Quittung”
has been pressed
Force activation
Is deactivated,
0 – 10 sec.
Is activated = If the pump has not been activated for 24 hrs, it will
automatically run for
duration of the set time.
Acoustic alarm
Is deactivated,
Is activated
Is activated = In case of a malfunction the internal piezo-buzzer
will sound
Intervall - Alarm
Is deactivated,
Is activated
Is activated = The fault information-relay will be synchronized
Instead of a flashing light it is possible to use a more economic
steady burning light
Thermal fault 1
Is deactivated,
Is activated
Is deactivated = There is no bimetallic contact (alarm contact)
connected to terminal 20,21.
Rot. Field fault
Is deactivated,
Is activated
Is activated = in case the phase sequence is wrong or if L2/L3 have
been missed an alarm will be triggered and the pumps cannot be
activated.
Light autom. Off
Is shut off,
is activated
If no further settings are actuated on the device, the background
lighting switches off automatically after 2 minutes.
ATEX - Mode
Is deactivated,
Is activated
Is activated = If no liquid can be measured by the level sensor the
pumps cannot be activated. This is valid for the Manual mode as
well as the Forced activation and the remote-control systems.
Service - Mode
Is activated,
Is deactivated
Is activated = All settings can be adjusted
Is deactivated= Settings are shown but cannot be adjusted
Level Control
Intern. converter
Floating switch
4 – 20 mA Interface
Determination of level by impact pressure or air supply.
Determination of level by floating switch
Determination of level by external sensor ( 4 – 20 mA)
20mA =>Level
0 – 1000 cm
The effective range of the external level sensor can be adjusted
Language
German - English
The displayed language can be adjusted