Installation and commissioning manual
MDX-I/O M2M
Additional Input/Output module with Datalogger function
COMMISSIONING
26
5146 en - 2014.03 / a
LEROY-SOMER
19.69
: MDX-I/O module reset
Reserved.
19.70
: Trigger state n°1
Adjustment range : Inactive (0) or Active (1)
Format
: 8-bit
This parameter indicates the state of trigger
output 1.
19.71
: Trigger 1: minute, second
Adjustment range : 00.00 to 59.59
Factory setting
: 00.00
Format
: 16-bit
Used to set the minutes and seconds when
the state of trigger circuit 1 (
19.70
) will
change to Active (1).
The 2 digits before the decimal point set the
minutes, and the 2 digits after the decimal
point set the seconds.
19.72
: Trigger 1: day of the month,
hours
Adjustment range : 1.00 to 31.23
Factory setting
: 1.00
Format
: 16-bit
Used to set the day of the month and hour
when the state of trigger circuit 1 will change
to Active (1).
The 2 digits before the decimal point set the
day of the month, and the 2 digits after the
decimal point set the hour.
19.73
: Trigger 1: months, years
Adjustment range : 01.04 to 12.99
Factory setting
: 01.04
Format
: 16-bit
Used to set the month and year when the state
of trigger circuit 1 will change to Active (1).
The 2 digits before the decimal point set the
month, and the 2 digits after the decimal point
set the year.
19.74
: Trigger-Mode 1
Adjustment range : Reset/None (0), At date (1),
Hourly (2), Daily (3),
Monthly (4),
Factory setting : Reset/None (0)
Format
: 8-bit
Used to select the frequency of trigger
circuit 1.
Reset/None (0):
Trigger 1 is inactive. This setting resets
parameter
19.70.
At date (1):
Tripping only at the time programmed by
parameters
19.71
to
19.73
.
Hourly (2):
Tripping on the hour at fixed minutes and
seconds, at the time programmed by
parameter
19.71
.
Daily (3):
Tripping every day at a fixed time (hour, minute
and second) at the time programmed by
parameters
19.71
and
19.72
.
Monthly (4):
Tripping every month at a fixed date and time
(day of the month, hour, minute and second)
at the time programmed by parameters
19.71
and
19.72
.
Note:
For each tripping mode, set
19.71
to
19.73
to determine the start of the cycle and
19.75
and
19.76
to set the duration (see
section 4.2 for operational examples).