7
LEROY-SOMER
InstallatIon and maIntenance
LSA 40 - 4 POLES
ALTERNATORS
4455 en - 10.2009 / a
Connection code
L.L voltage
Factory connection
L1(U)
N
L3(W)
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L2(V)
A
3 phases
3 phases
Winding
60 Hz
50 Hz
190 - 208
190 - 240
220 - 230
-
-
190 - 208
6
7
8
N
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L1(U)
L3(W)
L2(V)
D
F
L1(U)
M
L3(W)
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L2(V)
Tension LM = 1/2 tension LL
LM voltage = 1/2 LL voltage
R 220 voltage sensing:
0 => (T8) / 110 V => (T11)
R 438 voltage sensing:
0 => (T3) / 220 V => (T2)
N
L1(U)
L2(V)
L3(W)
NDE
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
Winding
60 Hz
50 Hz
380 - 415
380 - 480
440 - 460
-
-
380 - 416
6
7
8
R 220 voltage sensing:
0 => (T8) / 110 V => (T11)
R 438 voltage sensing:
0 => (T3) / 380 V => (T2)
NDE
N
L1(U)
L2(V)
L3(W)
L1(U)
L2(V)
L3(W)
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
1 phase
1 phase
or
3 phases
FF
Winding
60 Hz
50 Hz
220 - 240
220 - 240
220 - 240
200
250 - 260
-
6
7
8
R 220 voltage sensing:
0 => (T1) / 110 V => (T4)
R 438 voltage sensing:
0 => (T8) / 220 V => (T11)
NDE
M
L
L
L
L
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
Winding
60 Hz
50 Hz
220 - 240
220 - 240
220 - 240
200
250 - 260
-
6
7
8
NDE
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
L
L
L
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L
M
Tension LM = 1/2 tension LL
LM voltage = 1/2 LL voltage
R 220 voltage sensing:
0 => (T8) / 110 V => (T11)
R 438 voltage sensing:
0 => (T3) / 220 V => (T2)
Physical and visual checks
3.2.1 -
Before starting the machine for the first time, check that:
- the fixing bolts on the feet are tight
- the cooling air is drawn in freely
- the protective louvres and housing are correctly in place
- the standard direction of rotation is clockwise as seen from
the shaft end (phase rotation in order 1 - 2 - 3). For anti-
clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the site operating
voltage (see section § 3.3).
Terminal connection diagrams
3.3 -
To modify the connection, change the position of the terminal
cables. The winding code is specified on the nameplate.
Any intervention on the alternator terminals during
reconnection or checks should be performed with
the machine stopped.