Unidrive M200-201 Quick Start Guide
9
Issue Number: 7
Table 3-1 Tools required
Table 3-2 Recommended torque settings
Table 3-3 Tightening torque for mounting feet
Derating for reduced clearances is to be applied in addition to the derating for increased
switching frequency if operating above 3 kHz. Refer to the
Power Installation Guide
for the
current derating due to an increase in switching frequency.
If Din rail mounting is used in an installation, then mounting screws should be used to
secure the drive to the back plate.
Tool
Location
Size 1 Size 2 Size 3 Size 4
Small terminal screwdriver
Control, relay terminals
9
9
9
9
3 mm Flat-bladed screwdriver
Power terminals
9
5 mm Flat-bladed screwdriver
Terminal cover
9
9
9
9
4 mm Flat-bladed screwdriver
AC power terminals
9
Philips screwdriver
Power terminals
9
9
9
Torx 10 driver
EMC & MOV screws
9
9
9
9
Torx 15 driver
Fan screw
9
Torx 20 driver
Fan screw
9
9
9
Model size
Terminal block
description
Torque settings
All
Control terminals
0.2 N m (0.15 Ib ft)
Relay terminals
0.5 N m (0.37 Ib ft)
Ground terminals
1.5 N m (1.10 Ib ft)
1
Power terminals
0.5 N m (0.37 Ib ft)
2, 3, 4
1.4 N m (1.03 Ib ft)
Drive size
Tightening torque
1 to 3
1.3 N m (1 lb ft) to 1.6 N m (1.2 lb ft)
4
2.5 N m (1.8 lb ft) to 2.8 N m (2.1 lb ft)
NOTE
NOTE