INSTALLATION AND OPERATION

4.1 Installation

Installation of the Wise33 / Wise MP33 series AVR must be done by professional technicians only.

Before installation, please read this userís guide carefully.

4.1.1 Transportation

You can move the Wise33 / Wise MP33 series AVR by forklift truck.  In case that you have to lift it,

please consider

4.1.1.1

The AVR must be lifted upright at all time.  Do not tilt.

4.1.1.2

Do not unpack the packaging until it reaches the installation site to protect the damages

during transportation.

4.1.2 Wire sizing

4.1.2.1

For safety and neatness, it is recommended to wire all wires in the conduit.

4.1.2.2

The wire size recommended in the table below is TIS no. 11-2531 PVC insulated copper wire

with conductor temperature 70 degree Celsius, 700 Volts, ambient temperature 40 degree

Celsius and maximum 3 wires wiring in the same conduit.

Note: The maximum length of the wires mentioned above is 5 meters.  If you need to wire longer than 5

meters, the wire size must be increased.  Contact us if you need assistance.

4.1.3 Wire the upper and lower decks (Type B only).

4.1.3.1

Wire PE (Earth) terminal of the upper deck to PE (Earth) terminal of the lower deck.

4.1.3.2

Wire N2 and N3 (Neutral) terminals of the lower deck to N of the CONNECT TERMINAL of the

upper deck.

4.1.3.3

Wire INPUT2 terminal of the lower deck to INPUT2 terminal of the upper deck.

4.1.3.4

Wire OUTPUT2 terminal of the lower deck to OUTPUT2 terminal of the upper deck.

4.1.3.5

Wire INPUT3 terminal of the lower deck to INPUT3 terminal of the upper deck.

4.1.3.6

Wire OUTPUT3 terminal of the lower deck to OUTPUT3 terminal of the upper deck.

4.1.4 Connect the OUTPUT terminal of the Wise33 / Wise MP33 series AVR to the loads as following:

N terminal connects to Neutral.

L1 terminal connects to R-phase or Line1 from loads.

L2 terminal connects to S-phase or Line2 from loads.

L3 terminal connects to T-phase or Line3 from loads.

4.1.5 Connect the INPUT terminal of the Wise33 / Wise MP33 series AVR to main electricity supply as

following:

PE terminal connects to Ground (Earth).

N terminal connects to Neutral.

L1 terminal connects to R-phase or Line1 of main electricity supply.

L2 terminal connects to S-phase or Line2 of main electricity supply.

L3 terminal connects to T-phase or Line3 of main electricity supply.

- 13 -

Rating

10kVA 15kVA 24kVA 30kVA 45kVA 60kVA 75kVA 90kVA 120kVA 150kVA 180kVA 210kVA 240kVA

Input wire (mm

2

)

4

6

10

16

25

35

50

2  x  35 2 x 50

2 x 50

3 x 70

3 x 70

3 x 70

Output wire (mm

2

)

4

6

10

16

25

35

50

2  x  35 2 x 50

2 x 50

2 x 70

3 x 70

3 x 70

Connect wire (mm

2

)

-

-

-

-

25

35

50

-

-

-

-

-

-

Earth wire (mm

2

)

2.5 to 4

4

4 to 6

6

10

10

16

25

25

35

35

35

35

Содержание Wide33

Страница 1: ...LEN MAN STA 104 Rev 3 00 2008 ZERO CURRENT VOLTAGE CROSSING AUTOMATIC VOLTAGE STABILIZER WiseMP33 Wise33...

Страница 2: ...CONTENTS SAFETY INSTRUCTIONS 1 INTRODUCTION 2 FRONT AND REAR PANELS 4 INSTALLATION AND OPERATION 13 DATA DISPLAY 15 SETTING 17 TROUBLESHOOTING 18...

Страница 3: ...nly qualified electricians should install or service this unit 1 1 4 Properly install and ground the equipment in accordance with the instruction manual 1 1 5 To reduce risk from electric shock when y...

Страница 4: ...mended to connect through MDB Main Distribution Board 1 3 11During heavy rain and storm it is recommended to stop using any equipment including the AVR to prevent them from lightning through AC Line I...

Страница 5: ...load input frequency fault over temperature and etc it will shut itself down and restart automatically when it returns to normal for autotomatic restart mode only Maintenance bypass mode When the Main...

Страница 6: ...REAR PANELS 3 1 Front panel Wise33 Wise MP33 series AVR type A 3 1 3 3 1 2 3 1 1 3 1 4 1 3 1 4 2 3 1 4 3 3 1 4 4 3 1 5 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 A V L1 0 L3 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 A V...

Страница 7: ...Wise33 Wise MP33 series AVR type B 5 L1 0 L3 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 V A Upper Deck Lower Deck 3 1 5...

Страница 8: ...Wise33 Wise MP33 series AVR type B when open the upper door 6 3 1 1 3 1 2 L1 0 L3 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 V A 3 1 3 3 1 4 1 3 1 4 2 3 1 4 3 3 1 4 4 Upper Deck Lower Deck...

Страница 9: ...3 1 3 3 1 2 3 1 4 1 3 1 4 2 3 1 4 3 3 1 4 4 3 1 1 3 2 4 3 2 3 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 A V L1 0 L3 3 2 1 Wise33 Wise MP33 series AVR type C 7...

Страница 10: ...ise33 Wise MP33 series AVR type D when open the lower door 8 3 1 3 3 1 4 1 3 1 4 2 3 1 4 3 3 1 4 4 L1 N L2 N L2 L3 L3 N L3 L1 L1 L2 A V L1 0 L3 3 1 2 3 1 1 3 2 4 3 2 5 3 2 1 3 2 3 Upper Deck Lower Dec...

Страница 11: ...screen displays electrical data such as voltage current frequency and the percentage of AVR capacity taken by loads and etc 3 1 3 4 CONTROL BUTTONS The buttons to select display change setting and co...

Страница 12: ...phase 3 1 5 Door Relationship between indicator lamps and AVR operation 3 2 Inside Rear panel 3 2 1 RS 232 PC The port to connect signal to computer 3 2 2 CONNECT TERMINAL The terminal for connecting...

Страница 13: ...Wise33 Wise MP33 series AVR type A 11 3 2 4 3 2 3 3 2 1...

Страница 14: ...Wise33 Wise MP33 series AVR type B 12 3 2 1 3 2 2 3 2 2 3 2 4 3 2 3...

Страница 15: ...of the lower deck to N of the CONNECT TERMINAL of the upper deck 4 1 3 3 Wire INPUT2 terminal of the lower deck to INPUT2 terminal of the upper deck 4 1 3 4 Wire OUTPUT2 terminal of the lower deck to...

Страница 16: ...restart mode you will hear the audible alarm Press simultaneously once 4 2 6 Turn on all connected loads 4 3 Turn off the AVR 4 3 1 Turn off all connected loads 4 3 2 Open the door 4 3 3 Turn off the...

Страница 17: ...once Shows output voltage of each phase Line Neutral Press twice Shows output voltage of each phase Line Line Press 3 times Shows output current of each phase Line Neutral Press 4 times Shows load pe...

Страница 18: ...y returns to the first screen See more information in Section TROUBLESHOOTING 5 5 Press two buttons simultaneously 16 Press to start the AVR for manual restart mode only or return to main menu during...

Страница 19: ...he last digit of the password Refer to the above sample it is 8 6 1 6 Press simultaneously once to confirm password entry 6 1 7 Now you reach main setting menu Press to select setting item 6 2 System...

Страница 20: ...shuts itself down due to fault The output voltage is fault The input voltage is fault The input frequency is fault The voltage of main electricity supply is low There is fault Solutions Find out the c...

Страница 21: ...ly once AVR will restart when it detects no fault Check the AVR ventilation whether anything is blocking Disconnect some loads due to the AVR is overload Check the AVR ventilation whether anything is...

Отзывы: