SHUTDOWN indicator is lit,

ALARM indicator blinks,

OVER TEMP./FAULT is lit or

blinks and alarm sound.

Once the UPS started,  UPS

alarms a short beep sound

periodically.

The UPS operates normally

but sound a short beep

peroidically or the UPS

supplies backup power for a

short time and returns to

normal operating.

Blackout occured and UPS

supplies backup power.

But when the utility power

returns to normal, the

UPS still supplies backup

power.

Once start-up the UPS, any

circuit breaker has tripped.

The UPS operates normally

but does not supplies

power to loads.

Power source is normal but

the UPS supplies backup

power.

Symptoms

Possible causes

Solutions

The UPS is over temperature.

The UPS has fault.

The UPS has fault.

A power sag occurred in too short a

period for the user to sense. But the

UPS can detect that abnormal

condition.

The input voltage is out of range which

is too high or too low voltage.

UPS is overloaded or short circuited or

the circuit breaker is improper rating.

OUTPUT circuit breaker (if available) is

turned off.

OUTPUT FUSE is blown.

INPUT circuit breaker is turned off.

INPUT FUSE is blown (if available).

1. Press ON button to mute the alarm

       sound.

2. Turn off loads.

3. Press OFF button to shutdown the UPS.

4. Wait until the temperature is cool then

    restart the UPS again.

1. Press ON button to mute the alarm

      sound.

2. Press  

  button to view fault events.

   Then contact service center.

1. Press ON button to mute the alarm

    sound.

2. Press 

 button to view fault events.

    Then contact service center.

  No need to do anything.

1. Press ON button to mute alarm sound.

2. Turn off loads and wait until the input

    power is in the acceptable range (the

    UPS operates normally) then turn on

      loads again.

1. Turn off the UPS.

2. Recalculate and verify the system.

3. Check circuit breaker rating.

4. If the circuit breaker trips again when

    restart the UPS, contact service center.

Turn on OUTPUT circuit breaker

(if available).

1. Turn off the UPS

2. Check if the fuse is blown, replace new

  one with same type and rating.

Turn on INPUT circuit breaker.

1. turn off the UPS

2. Check if the fuse is blown, replace new

  one with same type and rating.

Содержание NB S-series

Страница 1: ...USER S GUIDE LEN MAN UPS 146 Rev 2 00 2009...

Страница 2: ...5 4 When UPS is overloaded 18 5 5 No load shutdown mode 18 5 6 Economy mode 18 5 7 Sleep mode 18 5 8 UPS self test 18 5 9 Self test cancellation 18 5 10 Mute alarm sound 19 5 11 Force bypass 19 5 12 M...

Страница 3: ...ONLY a certified electrician to wire your system permanently 1 1 4 Periodically check your cable outlets and power source to make sure that they are in good condition 1 1 5 To reduce risk from electr...

Страница 4: ...and eyes 1 3 5 Replace batteries with the same type and rating and follow the proper battery replacement procedure 1 3 6 When replacing a battery use tools with insulated handles and remove any watch...

Страница 5: ...tery option Manual self test RS 232 communication port Sealed lead acid maintenance free battery LED indicator and LCD display 2 3 UPS Operation 2 3 1 When utility power and loads are normal Above dia...

Страница 6: ...as blackout brownout under voltage over voltage or frequency fault and UPS has less than 100 load UPS draws backup power from battery to invert to AC power and continuously supplies to load 2 3 4 Use...

Страница 7: ...out of range 3 1 6 BYPASS indicator Indicates status of bypass power source Lit means the voltage and frequency of the bypass power source is in the range Off means the voltage of the bypass power so...

Страница 8: ...over 100 The UPS is overloaded Recommend to reduce some loads 3 1 13 BATTEY LEVEL indicator Indicates the level of battery power comparing to the full level The indicator shows from replace battery b...

Страница 9: ...T DO NOT TURN THE BATTERY CIRCUIT BREAKER ON BEFORE PRE CHARGE UPS AS IT MAY CAUSE DAMAGE TO THE UPS PRESS AND HOLD PRECHARGE BUTTON FOR 15 SECONDS AND THEN TURN ON THE BATTERY CIRCUIT BREAKER DO NOT...

Страница 10: ...8 Rear panel of NBP 3KS NBP 5KS and NBP 6KS UPS...

Страница 11: ...Front panel of NBP 8KS and NBP 10KS UPS 9...

Страница 12: ...Rear panel of NBP 8KS and NBP 10KS UPS 10...

Страница 13: ...ignal NO contact of K5 relay 3 2 5 10 K6 NO Overload signal NO contact of K6 relay 3 2 5 11 K7 NO NC Alarm signal NO and NC contacts of K7 relay 3 2 6 SNMP AGENT option The socket for connecting compu...

Страница 14: ...d the UPS to enable easyaccess for installation operation and maintenance 4 1 5 3 Install at the floor that is capable of supporting the weight of the UPS 4 1 5 4 Battery Extension Modules must be ins...

Страница 15: ...15 SECONDS AND THEN TURN ON THE BATTERY CIRCUIT BREAKER DO NOT CONNECT OR DISCONNECT THE CABLE TO THE BATTERY EXTENSION MODULE BEFORE YOU HAVE TURNED THE BATTERY CIRCUIT BREAKER OFF DO NOT TURN THE B...

Страница 16: ...BREAKER BYPASS INPUT CIRCUIT BREAKER Computer SNMP HTTP Network Remote Panel or Monitoring Main Power Supply L N Bypass Power Supply option L N AC Loads Battery Extension Modules option Installation...

Страница 17: ...ption Note For the single power source it has to jump the cables between BYPASS INPUT terminal and MAIN INPUT terminal of the UPS as shown in the installation diagram figures If there are two power so...

Страница 18: ...ce at INPUT terminal of the UPS Connect NEUTRAL at N terminal of the UPS and connect LINE at L terminal of the UPS If there is single power source jump BYPASS input terminal to INPUT terminal If there...

Страница 19: ...fore precharge the UPS because the UPS may be damaged Note In case of battery extension turn on BATTERY circuit breaker or FUSE circuit breaker if available of the battery extension unit before pressi...

Страница 20: ...urce fails 5 7 Sleep mode Sleep mode is an energy saving mode In this operating mode UPS transfer loads to consume power from bypass power source and stop the INVERTER operation when UPS found no conn...

Страница 21: ...user that loads are consuming power directly from bypass power source 5 12 2 Turn the MAINTENANCE MANUAL BYPASS switch to position BYPASS B MAINTENANCE BYPASS indicator is lit 5 12 3 Press and hold O...

Страница 22: ...SS INPUT voltage and input frequency Displays the set value of high and low BYPASS INPUT voltage Displays the set value of maximum and minimum acceptable input voltage of the UPS Displays the setting...

Страница 23: ...acity Return to the first screen 6 3 button 6 3 1 Press buttons once 6 3 2 Press buttons once again 6 3 3 Press buttons once again 6 3 4 Press buttons once again 6 3 5 Press buttons once again 6 3 6 P...

Страница 24: ...run R Receive command via RS 232 or remote terminal P Self test passed F Self test failed M Manual control Displays date time and fault event Press or button to view other events 6 4 1 Press buttons o...

Страница 25: ...certified technicians only 7 1 Enter password User must enter the password before change the system control set value Press and buttons simultaneously for 3 seconds To confirm the new set value press...

Страница 26: ...nce 7 2 3 Press button once again 7 2 4 Press button once again 7 2 5 Press button once again 7 2 6 Press button once again 7 2 7 Press button once again 7 2 8 Press button once again 7 2 9 Press butt...

Страница 27: ...Confirms to enter time setting Sets hour Confirms new time hour Sets minute Confirms new time minute Sets second Confirms new time second 7 3 1 Time setting 7 3 2 Date setting 7 3 2 1 Press and butto...

Страница 28: ...4 8 Press button once again Enters system control setting Enters system data setting Confirms to enter system data setting and displays set value of low bypass input voltage Displays special converter...

Страница 29: ...ries and recharge them immediately when the power is low If the UPS is not used or keep for long time recharge the UPS for 8 hours every 3 months Follow the following the procedure below to recharge t...

Страница 30: ...y power The UPS supplied power from battery until the battery power is very low and then the UPS shuts down automatically Battery capacity is too low and need to be replaced UPS is overloaded The UPS...

Страница 31: ...aker is improper rating OUTPUT circuit breaker if available is turned off OUTPUT FUSE is blown INPUT circuit breaker is turned off INPUT FUSE is blown if available 1 Press ON button to mute the alarm...

Страница 32: ...shown on screen 10 6 After finished the Easy Mon X installation restart the computer 10 7 Start the Easy Mon X Setup program and then click the Auto Detect UPS to search for the UPS model and communi...

Отзывы: