Technical data
POWERLINK communication data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2
POWERLINK communication data
Communication time
The communication time is the time between the start of a request and the arrival of the
corresponding response.
The communication times in an POWERLINK network depend on the ...
• processing time in the inverter;
• frame runtime (baud rate / frame length);
• nesting depth of the network.
Processing time inside the inverter
There are no interdependencies between parameter data and
process data
.
Range
Values
Min. cycle time
400
μ
s
Total cycle times
0.4 / 0.5 / 1.0 / 1.2 / 2.0 / 3.0 … 20.0 ms
Buffer size
• Tx-iso: max. 1490 bytes
• Rx-iso: max. 1490 bytes
Delay time
• Controlled node (T
Preq
- T
Res
): approx. 2.6
μ
s
• Controlled node (T
SoA
- T
ASnd
): approx. 2.6
μ
s
Frame size
Max. asynchronous frame size (MTU): 1518 bytes
SDO communication method
UDP/IP or ASND
Number of RPDOs
1 channel
RPDO user data per application
Max. 6 objects (max. 10 bytes)
Number of TPDOs
1 channel (data access of all nodes by broadcasting)
TPDO user data per application
Max. 6 objects (12 bytes)
CN operating modes
Support of ...
• Multiplex CNs
• Optional CNs
Data
Processing time
Process data
Approx. 2 ms
+ 0 ... 1 ms
+ 1 ... x ms
Update cycle
Processing time in the module
Runtime of the application task of the technology
application used (tolerance)
Parameter data
Approx. 30 ms + a tolerance of 20 ms (typically)
Some codes may require a longer processing time (see reference manual/
online help for Inverter Drive 8400 motec).