Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01121
C01122
C01123
Parameter | Name:
C01121 | Sync cycle time setpoint
Data type: UNSIGNED_16
Index: 23454
d
= 5B9E
h
From version 04.00.00
Cycle time setpoint for device synchronisation
• Time interval at which the phase control loop (PLL) in the inverter expects the synchronisation signals.
• The cycle time setpoint must be set according to the cycle of the respective synchronisation source.
Note:
• Only integer multiples of 1000
μ
s can be set.
• Intelligent communication modules usually define the cycle time setpoint derived from the bus cycle. In this
case, a manual change is not possible.
Example: For the CAN bus, a distance of 2 ms has been set between two synchronisation signals. If the CAN bus is
to be used as synchronisation source, a synchronisation cycle of 2000
μ
s must be set in C01121.
Synchronisation of the internal time base
Setting range
(min. value | unit | max. value)
Lenze setting
1000
μ
s
20000
1000
μ
s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C01122 | Sync phase position
Data type: UNSIGNED_16
Index: 23453
d
= 5B9D
h
From version 04.00.00
Phase position for device synchronisation
• The phase position determines the zero-time of the internal system cycle with regard to the synchronisation
signal (bus cycle). Since PDO processing is an inherent part of the system part of the application, the instant of
acceptance of the PDOs is postponed as well by a changed phase position.
• With a setting = 0, the system cycle starts simultaneously with the synchronisation signal.
• With a setting > 0, the internal system cycle starts earlier by the set time with regard to the synchronisation
signal (the phase position acts negatively).
• Intelligent communication modules define the optimal time with activated synchronisation by themselves. In
this case, a manual change is not possible.
• The decisive factor for defining C01122 is the time where all nodes are provided with valid PDOs.
Example: If the phase position is set to 550
μ
s, the system part of the application starts 550
μ
s before the arrival of
the synchronisation signal.
Synchronisation of the internal time base
Setting range
(min. value | unit | max. value)
Lenze setting
0
μ
s
1000
0
μ
s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C01123 | Sync window
Data type: UNSIGNED_16
Index: 23452
d
= 5B9C
h
From version 04.00.00
Time slot for monitoring the synchronisation signal or the phase position
• The synchronisation signal or the current phase position must be within this time slot around the corresponding
expected value (
• With the setting "1000
μ
s" there will be no monitoring.
Synchronisation of the internal time base
Setting range
(min. value | unit | max. value)
Lenze setting
0
μ
s
10000
100
μ
s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1