8400 BaseLine D | Software Manual
Error management
Monitoring
128
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
7.4.1
Setting the error response
When a monitoring function responds, the response set for this monitoring function
(troubleQSP, warning, fault, etc.) will be activated.
For many monitoring functions the response can be individually parameterised via
parameters.
Tip!
The table in chapter "
" contains the error messages for
which the response can be set
Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g.
temperature) has been exceeded.
The corresponding preset threshold values can be changed via the following
parameters:
7.4.2
Monitoring of the device utilisation
, the device utilisation (i x t) over the last 180 seconds is displayed in [%].
If the value displayed in
exceeds the warning threshold set in
, the error
message "Device utilisation Ixt >
C123
" is output and the error response set in
occurs (default setting: "Warning").
If the value displayed in
exceeds 100 %, the error message "device utilisation Ixt
> 100 %" is output and the error response "fault" occurs.
– The error can only be reset if the value displayed in
is < 95 % again.
Parameter
INFO
Motor overload protection (I²xt)
Device util. warning threshold
Undervoltage (LU) threshold