16.1.6.7
Fault reaction active
This device state becomes active if a minor fault occurs. This means that the inverter is still
able to drive the motor in a controlled way.
•
The inverter is brought to a standstill irrespective of the setpoint specified with the decel-
eration (
) set for quick stop.
If the inverter is at standstill, a change to the "
" device state take place automati-
cally.
•
Only the parameters of the inverter can be changed that do not require an inverter disa-
ble.
•
If the internal holding brake control (
) is active in the inverter, the motor brake
is closed.
•
The drive control is active.
1
From all states
2
Power section inhibited (pulse inhibit)
3
Power section enabled
Bit pattern in the CiA 402 status word (
Bit 15 ... 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
(specific)
Warning
active
Operation
inhibited
Quick stop
active
DC bus ready
for operation
Fault active
Operation
enabled
Switched on
Ready to
switch on
X
X
0
X
X
1
1
1
1
X = state is not relevant
Configuring the network
Device profile CiA 402
Device states
332