Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
111
Implemented CIP™ objects
General CIP objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.1
General CIP objects
14.1.1
Identity Object (1 / 0x01)
The "Identity Object" provides the identification and general information about the device.
Class attributes
Instance attributes
Attribute
ID
Service
Name
Data type
Value
1
Get
Revision
UINT
1 (0x0001)
2
Get
Max. Instance
UINT
1 (0x0001)
3
Get
Number of Instances
UINT
1 (0x0001)
6
Get
Max. ID Number Class
Attributes
UINT
7 (0x0007)
7
Get
Max. ID Number Instance
Attributes
UINT
8 (0x0008)
Attribute
ID
Service
Name
Data type
Value
1
Get
Vendor ID
UINT
587 (0x024B)
2
Get
Device Type
UINT
2 (0x0002): AC Drive
3
Get
Product Code
UINT
8440 (0x20F8)
4
Get
Revision:
STRUCT of:
Firmware revision of the device
Major Revision
USINT
Minor Revision
USINT
5
Get
Status
WORD
Current device status (status bits)
•
Instance attribute "Status" (attribute 5)
•
6
Get
Serial Number
UDINT
Serial number of the device
7
Get
Product Name
SHORT_STRING
E84DGFCG
8
Get
State
USINT
Current device state:
• 0: Nonexistent
• 1: Device self-testing
• 2: Standby
• 3: Operational
• 4: Major recoverable fault
• 5: Major unrecoverable fault
• 6 ... 254: Reserved
• 255: Standard for "Get_Attributes_All"
service
(See also
)