Technical data
2
EDKRBM390R DE/EN/FR/ES/IT 2.0
21
H1_Daten−BemDaten_Leg
2
Technical data
Operating conditions
Climatic conditions
Class 3K3 to
EN 50178
Without condensation,
average relative
humidity 85
%
Ambient temperature
−10 °C ... +55 °C
Above 45 °C the permanent power P
d
is to
be reduced by 2.5 %/°C
Installation height
0 ... 4000 m amsl
Above 1000 m the permanent power P
d
is to
be reduced by 5 %/1000 m
Mounting location
l
In the control cabinet
l
The mounting location must comply
with the device features mentioned in
the chapter "General data".
l
Flammable materials or substances
must not be placed in the vicinity of the
brake resistor.
l
The heat generated by the brake resistor
must be dissipated freely.
Mounting position
Vertically suspended with connecting cables
at the bottom.
Free spaces
at the top
> 200 mm
at the bottom
> 100 mm
to the sides
> 30 mm
Design and project
planning
l
Mean value of regenerative power
< permanent power P
d
of brake resistor.
l
Regenerative power during braking time
< thermal capacity C
B
of brake resistor.
l
Braking time < 10 % of cycle time
(braking time + dead time).
l
Always connect the thermal contact and
integrate it in a way into the system
monitoring that the mains supply will be
switched off when the basic device is
overheated.