Control connections
EDK10200EV3 DE/EN/FR 5.0
L
QM
Terminal Use
Level
Data
Voltage
supply
X1/
⊥
24
0 V of supply voltage,
ground for digital inputs
and outputs
-
-
X1/+24
Supply voltage
+18 VDC ... 30 VDC
-
X1/+O24 Supply voltage for digital
outputs
+18 VDC ... 30 VDC
-
Digital
inputs
X3/I1
Freely assignable input 1
HIGH active
Input current: 8 mA at 24 V
Reading and processing the
inputs
HIGH active
LOW: 0 V ... +4 V
HIGH: +13 V
+30 V
Reading and processing the
inputs: shortest reading cycle: 1
ms (depending on the site
X3/I8
Freely assignable input 8
HIGH: +13 V ... +30 V ms (depending on the site
where the process map is
generated)
Digital
outputs
X2/O1
Freely assignable output 1
HIGH active
Load capacity: max. 1 A per
output
outputs
HIGH active
LOW: 0 V ... +4 V
HIGH: +13 V
+30 V
output
Updating the outputs: shortest
update cycle is 1 ms (depending
X2/O4
Freely assignable output 4
HIGH: +13 V ... +30 V update cycle is 1 ms (depending
on the site where the process
map is generated)