Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
34
EDBCSXE040 EN 6.0
Assembly
ƒ
Connect the power supply modules, capacitor modules (optional), axis modules, RFI
filters, and mains chokes to the earthed mounting plate with a surface as large as
possible.
– Mounting plates with conductive surfaces (zinc−coated or stainless steel) allow
permanent contact.
– Painted plates are not suitable for an EMC−compliant installation.
ƒ
If you use the ECSxK... capacitor module:
– Install the capacitor module between the power supply module and the axis
module(s).
– If the total cable length in the DC−bus connection is > 5 m, install the capacitor
module as close as possible to the axis module with the greatest power.
ƒ
Use of several mounting plates:
– Connect as much surface of the mounting plates as possible (e.g. with copper
bands).
ƒ
Ensure the separation of motor cable and signal or mains cables.
ƒ
Avoid a common terminal/power strip for the mains input and motor output.
ƒ
Lay the cables as close as possible to the reference potential. Freely suspended
cables act like aerials.
Filters
Only use RFI filters and mains chokes which are assigned to the power supply modules:
ƒ
RFI filters reduce impermissible high−frequency interferences to a permissible value.
ƒ
Mains chokes reduce low−frequency interferences which depend on the motor
cables and their lengths.