Configuration
Configuring system bus (CAN)
Node guarding
102
EDBCSXE040 EN 6.0
8.2.7
Node guarding
The "Node Guarding" function is implemented as of operating system V3.0.
In case of cyclic node monitoring (Node Guarding) the CAN master regularly enquires the
states of the slaves participating in the monitoring process.
ƒ
The master starts the node guarding by sending the node guarding telegram.
ƒ
If the slave does not receive a node guarding telegram within the monitoring time
(Node Life Time), the "Life Guarding Event" is enabled (fault message "NodeGuard
Trp/Msg/Wrn").
Settings
In order that the power supply module takes over the function of the
"Node Guarding Slave", make the following settings:
1. Set C0352 = 2.
(The power supply module is configured as "Node Guarding Slave".)
2. Set the time interval of the status enquiry by the master (Node Guard Time) via
C0382.
3. Set the factor for the monitoring time (Node Life Time Factor) via C0383.
NodeLifeTime
+
NodeGuardTime(C0382)
@
NodeLifeTimeFactor(C0383)
4. Set the response to a "Life Guarding Event" via C0384.
Parameter
C0352
Designation
CAN master/slave boot−up configuration
Data type: INTEGER_32
Index: 24223
dec
= 5E9F
hex
Master/slave configuration for CAN bus interface X4
Note:
After the setting, a reset node is required.
Selection list
(Lenze setting printed in bold)
Information
0 Slave
1 Master (CAN network PDO enable)
2 Slave node guarding
Parameter
C0382
Designation
CAN Node Guarding: "Node Guard Time"
Data type: INTEGER_32
Index: 24193
dec
= 5E81
hex
Setting of the time interval for the status enquiry from the master
l
Only relevant if C0352 = 2.
102
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535
0 ms