Monitoring
functions
Overview of monitoring functions
9
194
EDBCSXS064
EN 4.0
9.2
Overview of monitoring functions
Monitoring
Possible fault responses
l
Lenze setting
ü
Can be set
Fault message
Description
Source
Code
TRIP
Message
Warning
Fail−QSP
Off
x071
CCR
System fault
Internal
l
x091
EEr
External monitoring (activated via DCTRL)
FWM
C0581
l
ü
ü
ü
ü
x191
HSF
Internal error
Internal
l
Voltage supply
1020
OU
Overvoltage in the DC bus (C0173)
MCTRL
l
1030
LU
Undervoltage in the DC bus(C0174)
MCTRL
l
0070
U15
Undervoltage of internal 15 V voltage supply
Internal
l
0107
H07
Internal fault (power section)
Internal
l
Communication
x041
AP1
Internal fault (signal processor)
Internal
l
x061
CE0
Communication error on the automation interface (AIF)
AIF
C0126
ü
ü
l
x062
CE1
Communication error on the CAN1_IN process data input object
(monitoring time adjustable via C0357/1)
CAN1_IN
C0591
ü
ü
l
x063
CE2
Communication error on the CAN2_IN process data input object
(monitoring time adjustable via C0357/2)
CAN2_IN
C0592
ü
ü
l
x064
CE3
Communication error on the CAN3_IN process data input object
(monitoring time adjustable via C0357/3)
CAN3_IN
C0593
ü
ü
l
x065
CE4
BUS−OFF state CAN bus at interface X4 (CAN)
(too many faulty telegrams)
CAN
C0595
ü
ü
l
x066
CE5
Communication error of the gateway function (C0370, C0371) via CAN bus
at interface X4 (CAN)
CAN
C0603
ü
ü
l
x122
CE11
Communication error on the CANaux1_IN process data input object ( time
monitoring adjustable via C2457/1)
CANaux1_IN
C2481
ü
ü
l
x123
CE12
Communication error on the CANaux2_IN process data input object ( time
monitoring adjustable via C2457/2)
CANaux2_IN
C2482
ü
ü
l
x124
CE13
Communication error on the CANaux3_IN process data input object ( time
monitoring adjustable via C2457/3)
CANaux3_IN
C2483
ü
ü
l
x125
CE14
BUS−OFF state CAN bus at interface X14 (CAN−AUX)
(too many faulty telegrams)
CANaux
C2484
ü
ü
l
x: 0 = TRIP, 1 = message, 2 = warning, 3 = FAIL−QSP
1)
Adjustable in the DDS under
Project
Exceptional handling
2)
For ECSxA... only