Electrical installation
EMC−compliant wiring
6
EDK94AYCET DE/EN/FR/ES/IT 5.1
39
H1_E_INST−EMV_E94AYCET_2192_LEG
6
Electrical installation
EMC−compliant wiring
In typical systems, standard shielding of the Ethernet cables is sufficient.
In environments with a very high level of interference, immunity to noise can be improved
by additionally earthing the cable shield on both sides.
Observe the following notes for this:
1. The clearance of the additional earthing from the Ethernet plug depends on the
module slot. The clearance is
– approx. 10 cm for the upper slot (MXI1);
– approx. 20 cm for the lower slot (MXI2).
2. Starting from this clearance, remove the plastic sheath of the cable on a length of
2 cm.
3. Mount the cable shield on the shield sheet of the Servo Drive 9400.
E94YCXX008
Connection to the shield sheet of the Servo Drive 9400
Continuing EtherCAT cable at X247 (OUT)
Incoming EtherCAT cable at X246 (IN)
Communication module in slot MXI1 of the Servo Drive 9400
Содержание E94AYCET
Страница 2: ...dummy_komponente ...
Страница 25: ...Diagnose LED Statusanzeigen 8 EDK94AYCET DE EN FR ES IT 5 1 25 H1_Diagnose status_LEDs_E94AYCET ...
Страница 26: ...EDK94AYCET DE EN FR ES IT 5 1 26 klappseite_E94AYCET Tab Legende_E94AYCET E94AYCET001B 0Fig 0Tab 0 E94AYCET017 ...
Страница 47: ...Diagnostics LED status displays 8 EDK94AYCET DE EN FR ES IT 5 1 47 H1_Diagnose DUMMYSEITEVOR ...
Страница 48: ...EDK94AYCET DE EN FR ES IT 5 1 48 klappseite_E94AYCET Tab Legende_E94AYCET E94AYCET001B 0Fig 0Tab 0 E94AYCET017 ...
Страница 69: ...Diagnostic Affichages d état par LED 8 EDK94AYCET DE EN FR ES IT 5 1 69 H1_Diagnose DUMMYSEITEVOR ...
Страница 70: ...EDK94AYCET DE EN FR ES IT 5 1 70 klappseite_E94AYCET Tab Legende_E94AYCET E94AYCET001B 0Fig 0Tab 0 E94AYCET017 ...
Страница 90: ...EDK94AYCET DE EN FR ES IT 5 1 90 klappseite_E94AYCET Tab Legende_E94AYCET E94AYCET001B 0Fig 0Tab 0 E94AYCET017 ...