Parameter | Name:
C14375 | CAN SDO client Rx identifier
Data type: BITFIELD_32
Index: 11200
d
= 2BC0
h
Identifier with which the corresponding SDO client can be reached.
• If bit 31 is set (0x8nnnnnnn), the corresponding SDO client channel is deactivated (see DS301, V4.02).
• The client channels need not be parameterised right now. Their functionality will only be required when using
the gateway services.
Identifiers of the parameter data objects (
Setting range
0x00000000
0xFFFFFFFF
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: SDO invalid
... ...
Bit 31 SDO invalid
Subcodes
Lenze setting
Information
C14375/1
0x80000000
SDO client channel 1 RX ... 10 RX
...
C14375/10
;
Read access
;
Write access
CINH
PLC STOP
No transfer
Scaling factor: 1
Parameter | Name:
C14376 | CAN SDO client Tx identifier
Data type: BITFIELD_32
Index: 11199
d
= 2BBF
h
Identifier with which the corresponding SDO client can carry out transmissions.
• If bit 31 is set (0x8nnnnnnn), the corresponding SDO client channel is deactivated (see DS301, V4.02).
• The client channels need not be parameterised right now. Their functionality will only be required when using
the gateway services.
Identifiers of the parameter data objects (
Setting range
0x00000000
0xFFFFFFFF
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: SDO invalid
... ...
Bit 31 SDO invalid
Subcodes
Lenze setting
Information
C14376/1
0x80000000
SDO client channel 1 TX ... 10 TX
...
C14376/10
;
Read access
;
Write access
CINH
PLC STOP
No transfer
Scaling factor: 1
Содержание E94AYCCA