Interruption of PROFINET communication
64
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10
Monitoring
10.1
Interruption of PROFINET communication
An interruption of PROFINET communication in the "Data_Exchange" state, e.g. by cable break or
failure of the I/O controller is recognised by the I/O device.
The response to the interruption of communication is controlled via the following settings:
1. During the initialisation of PROFINET communication the watchdog monitoring time
specified in the I/O controller (
) is transferred to the I/O device.
If the I/O device does not receive any valid process data in the "Data_Exchange" state, the
process data are treated according to the setting in
. (Like this the data that
were sent last by the I/O controller can be used or set to zero.)
After the watchdog monitoring time has elapsed, the I/O device changes to the
"No_Data_Exchange" status (see
), and the red LED
BE
is activated (
There is no response in the I/O device.
2. To trigger a response in the IO device, you have to set a
Reaction of the Inverter Drive 8400
motec
) additionally in the »»Engineer«« under the
Monitoring
tab.
By setting a
Reaction time delay
(
) you can decelerate this response.
• In the Lenze setting "0 ms", this monitoring is activated.
• With the setting "65535 ms", this monitoring is deactivated.
• A change of monitoring will be effective immediately.
• The monitoring time elapses when the "Data_Exchange" status is exited.
After this response delay has elapsed, the response set is executed with the error message
"
PROFINET: Data_Exchange status quit [0x01bc6531]
.