![Lenze E82ZWBRU Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/lenze/e82zwbru/e82zwbru_mounting-instructions_1882311042.webp)
6
Technical data
General data/Rated data
EDK82ZWBRU DE/EN/FR 2.0
L
42
General data
Conformity
CE
Low-Voltage Directive (37/23/EC)
Resistance to
vibration
Acceleration-proof to 2g
(Germanischer Lloyd, general conditions)
Climate
conditions
Class 3K3 according to EN 50178
(without moisture condensation, medium RH 85% )
Degree of
contamination
VDE 0110 Part 2 Degree of contamination 2
Temperature ranges
Transport
Storage
Operation
-25
°
C ... +80
°
C
-25
°
C ... +80
°
C
-20
°
C ... +60
°
C
Installation
in Lenze base units
RFI emission
Limit class A according to EN55011
Insulation resistance
Overvoltage category III according to VDE0110
Enclosure
IP65
Rating
Input voltage
1/N/PE AC 230 V, 45 Hz ... 65 Hz
3/PE AC 230 V, 45 Hz ... 65 Hz
3/PE AC 400 V, 45 Hz ... 65 Hz
3/N/PE AC 400 V, 45 Hz ... 65 Hz
3/N/PE AC 500 V, 45 Hz ... 65 Hz
Output voltage
DC 205 V
with mains voltage AC 230 V
Output voltage
DC 180 V / DC 205 V
with mains voltage AC 400 V
DC 257 V
with mains voltage AC 500 V
Brake current
max. 0.55 A
Power loss
max. 3 W
Control input
High (DC +12 ... 30 V)
Low (DC 0 ... +3 V)
(PLC level, HTL)
Brake switching
times
see technical data of the brake