![Lenze E82ZAFSC010 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/lenze/e82zafsc010/e82zafsc010_mounting-instructions_1882061044.webp)
Commissioning
Commissioning steps
EDK82ZAFSC−010 DE/EN/FR 6.1
44
H2_Inbetriebnahmeschritte−−−−(DUMMYSEITEVOR)−−−
Commissioning steps
Step
Procedure
Description
1.
Switch on the mains
voltage.
The basic device will be ready for operation after approx.
1 second.
The controller inhibit is active.
Drive response:
The green LED is blinking.
Keypad:
(if attached)
2.
Control digital inputs.
Lenze setting:
l
CW rotation:
– E1, E2, E3, E4: LOW
l
CCW rotation:
– E1, E2, E3: LOW
– E4: HIGH
Individual setting:
l
Adapt digital inputs under C0007 or C0410.
l
The digital inputs must be controlled so that the drive
can start via terminal after controller enable.
3.
Provide a setpoint
Lenze setting:
Setpoint: 0 ... +10 V
Individual setting:
l
Depending on the position of the DIP switch at the
function module
– apply master current to X3/8 or
– Apply master voltage at X3/8.
l
Check C0034.
4.
Release the controller via
the terminal.
Lenze setting:
X3/28 = HIGH (+12 ... +30 V)
Drive response:
l
The green LED is on.
l
Keypad:
goes off.
5.
The drive should be running now.