Safety instructions
Residual hazards
l
18
EDS700ACBA EN 5.1
Commissioning and operation
Before commissioning after longer storage periods, measure insulation resistance. In case
of values
£
1 k
W
per volt of rated voltage, dry winding.
For trial run without output elements, lock the featherkey. Do not deactivate the
protective devices, not even in a trial run.
Check the correct operation of the brake before commissioning lowvoltage machines with
brakes.
Integrated thermal detectors do not provide full protection for the machine. If necessary,
limit the maximum current. Parameterise the controller so that the motor will be switched
off with I > I
rated
after a few seconds of operation, especially at the risk of blocking.
Vibrational severities v
eff
£
3.5 mm/s (P
rated
£
15 kW) or 4.5 mm/s (P
rated
> 15 kW) are
acceptable if the clutch is activated.
If deviations from normal operation occur, e.g. increased temperatures, noises, vibrations,
find the cause and, if required, contact the manufacturer. In case of doubt, switch off the
lowvoltage machine.
If the machine is exposed to dirt, clean the air paths regularly.
Shaft sealing rings and roller bearings have a limited service life.
Regrease bearings with relubricating devices while the lowvoltage machine is running.
Only use the grease recommended by the manufacturer. If the grease drain holes are
sealed with a plug, (IP54 drive end; IP23 drive and nondrive end), remove plug before
commissioning. Seal bore holes with grease. Replace prelubricated bearings (2Z bearing)
after approx. 10,000 h 20,000 h, at the latest however after 3 4 years.
The product−specific safety and application notes given in these instructions must be
observed!!
2.3
Residual hazards
Protection of persons
ƒ
Before working on the controller, check whether all power terminals are deenergised
because
– depending on the controller − the power terminals U, V, W, +UG, −UG, Rb1, and Rb2
carry hazardous voltages for up to 3 to 30 minutes after power−off.
– the power terminals L1, L2, L3; U, V, W, +UG, −UG, Rb1 and Rb2 carry hazardous
voltages when the motor is stopped.
Device protection
ƒ
Connect/disconnect all pluggable terminals only in deenergised condition!
ƒ
Detach the controllers from the installation, e.g. from the rear panel of the control
cabinet, only in deenergised condition!
Содержание E70AC Series
Страница 1: ...EDS700ACBA Usx Usx Hardware Manual i700 l E70AC Servo Inverter i700 Translation...
Страница 2: ...0Fig 0Tab 0...
Страница 75: ...Mechanical installation 5 l 75 EDS700ACBA EN 5 1...
Страница 147: ...Accessories overview Terminals 11 l 147 EDS700ACBA EN 5 1 E70AZEVK001 i700ZM001 A...
Страница 148: ...Accessories overview Terminals 11 l 148 EDS700ACBA EN 5 1 E70AZEVK002 i700ZM001 C...
Страница 149: ...Accessories overview Terminals 11 l 149 EDS700ACBA EN 5 1 E70AZEVK003 i700ZM001 B...
Страница 150: ...Accessories overview Terminals 11 l 150 EDS700ACBA EN 5 1 E70AZEVK004 i700ZM001 D...
Страница 151: ...Accessories overview Terminals 11 l 151 EDS700ACBA EN 5 1 E70AZEVK005 i700ZP005 a...
Страница 152: ...Accessories overview Terminals 11 l 152 EDS700ACBA EN 5 1 E70AZEVK006 i700ZP005 b...
Страница 157: ...Accessories overview EMC accessories Shield mounting 11 l 157 EDS700ACBA EN 5 1 ezamb_001 EZAMBKBM 10 mm 8 30 mm...
Страница 161: ......