background image

 

11 

RG-MHBAC

BACnet Objects

4.7  Multi-State Input (MSI) Object Descriptions

Object MSI-1:  Operational Status
 

This object is for monitoring the actual operating condition of the drive. The value returned 
is a number between 1 and 16 which corresponds to one of the following operating states:

Value

Name

Operational State

1

LOCK

Fault Lockout

2

FAULT

Fault

3

PEND

Start Pending

4

STOP

Stop

5

BRAKE

DC Brake

6

RUN@0

Run At 0Hz

7

RUN

Run

8

ACCEL

Accelerating

9

DECEL

Decelerating

10

LIMIT

Current Limit

11

F DEC

Decel Override

12

INVAL

Invalid State

13

KSTOP

Keypad Stop

14

KSTOP

Alternate Keypad Stop

15

RSTOP

Remote (Terminal Strip) Stop

16

SSTOP

Serial Stop

Object MSI-2:  Present Fault

 

This object indicates the type of fault on which the drive is currently tripped. This object 
returns a value between 1 and 25 which corresponds to one of the following fault conditions:

Value Name

Fault

Value Name

Fault

1

NO FAULT

No Fault

14

CONTROL

Control Fault

2

OUTPUT

Output Fault

15

LANGUAGE

Language

3

E-STOP

E-Stop

16

EXTERNAL

External Fault

4

HI VOLTS

High DC Bus Volts

17

INTERNAL16 Internal Fault 16

5

HI TEMP

High Drive Temp

18

PWR TRAN

Power Transient

6

OVERLOAD Thermal Overload

19

INTERNAL18 Internal Fault 18

7

OUTPUT

Output Fault

20

INTERNAL19 Internal Fault 19

8

LO VOLTS

Low DC Bus Volts

21

INTERNAL20 Internal Fault 20

9

START ER

Start Error

22

INTERNAL21 Internal Fault 21

10

BRAKE ER

DC Brake Error

23

INTERNAL22 Internal Fault 22

11

FOLLOWER Follower Loss

24

INTERNAL23 Internal Fault 23

12

DB ERROR DB Error

25

SERIAL

Serial Comm Loss

13

PWR SAG

Power Sag

Содержание AC Tech MCH Series

Страница 1: ...MCH Series Drives BACnet Communications Guide...

Страница 2: ...nc 1791 Tullie Circle NE Atlanta GA 30329 http www bacnet org Modbus is a registered trademark of Schneider Electric founder of Modbus IDA http www modbus IDA org 2003 AC Technology Corporation No par...

Страница 3: ...ed Programming Parameters 4 3 2 Omitted Parameters and Selections 4 3 3 Modified Parameters and Selections 5 3 4 Serial Communication Setup 5 4 MCH BACnet Objects 8 4 1 BACnet Object Map 8 4 2 Analog...

Страница 4: ...n installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directi...

Страница 5: ...adapt the controller to your application as described in the documentation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connect...

Страница 6: ...length of an MS TP segment is 1200 meters 4000 feet with AWG 18 cable Maximum number of nodes unit loads per segment is 32 as specified by the EIA 485 standard Because MS TP uses non return to zero N...

Страница 7: ...e of bits 0 15 of the drive s 22 bit device number It can be used by itself to represent a device number in the range of 0 to 65535 If the device number exceeds 65535 then DEVICE NUM EX must also be u...

Страница 8: ...ng of all MCH BACnet points Write commands will not be accepted without proper modification to these drive settings One exception to this is STOP commands which are always accepted over the LAN For se...

Страница 9: ...erial watchdog timeout occurrence The options for this parameter are FAULT default and PRESET 3 If FAULT is selected and the drive is running when a serial watchdog timeout occurs the drive will trip...

Страница 10: ...of serial control If Drive Parameter 30 Control is set to SERIAL AUTO and the drive was running when the timeout occurred the drive will also stop the motor by tripping into a SERIAL FAULT A fault res...

Страница 11: ...ommand PID SETPOINT 1 00 50 AI 7 PID Feedback PID FEEDBACK 1 00 0 AV 1 Keypad Speed Command KEY SPD CMD Hz 0 01 20 00 AV 2 Keypad Setpoint Command KEY STPT CMD 1 00 50 BI 1 Run Stop Status RUN_STOP 1...

Страница 12: ...back This object is for monitoring the current PID Feedback value at the input specified by Drive Parameter 74 PID Feedback The range of this object is defined by Drive Parameter 75 Feedback Min and D...

Страница 13: ...information Object BI 6 Relay 1 This object monitors the state of the drive s Relay 1 output This object can be used to indicate various drive conditions as specified by Drive Parameter 54 RELAY1 Ref...

Страница 14: ...his object indicates the type of fault on which the drive is currently tripped This object returns a value between 1 and 25 which corresponds to one of the following fault conditions Value Name Fault...

Страница 15: ...is for monitoring the source of the speed setpoint reference States 1 through 9 are speed references States 10 through 18 are setpoint references This object must be in state 1 9 or 10 for the LAN to...

Страница 16: ...peed Source Selection This object mimics the functionality of the SPEED SOURCE key on the drive keypad It is used to determine whether the drive will get its speed setpoint reference from Drive Parame...

Страница 17: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG MHBAC e2...

Отзывы: