Commissioning
4
Commissioning
4.1
Conditions
4.1.1
Electrical requirements
The external voltage source must be able to drive a current
>
1 A because it supplies the control
electronics of the controller (back-up in the event of power failure): Even after the power supply has
been disconnected:
•
actual values are recorded and processed
•
the control electronics remain reliable
4.1.2
Necessary changes to the default setting
For troublefree operation of the examples
(
^
6, ff)
the default setting of the controller must be
changed as follows:
•
Motor standstill must be assigned to the digital
output terminal A1
Code C0117/1, selection 10650
•
TRIP display must be assigned to the digital
output terminal A2
Code C0117/2, selection 15000
•
“
HIGH
”
active must be assigned to digital output
terminal
Code C0118/1, selection 0
Excerpt from code table
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
[C0117]
1
2
3
4
CFG: DIGOUT
CFG: DIGOUT
CFG: DIGOUT
CFG: DIGOUT
*
15000
10650
500
5003
DCTRL-TRIP
CMP1-OUT
DCTRL-RDY
MCTRL-MMAX
Signal configuration DIGOUT
X5/A1
X5/A2
X5/A3
X5/A4
*
depending on C0005
C0118
1
2
3
4
DIGOUT pol
DIGOUT pol
DIGOUT pol
DIGOUT pol
1
1
0
0
0
1
High active
Low active
Terminal polarity DIGOUT
X5/A1
X5/A2
X5/A3
X5/A4
Caution!
Time for controller-internal QSP ramp = t
QSP
(code C0105) must not be set too short!
If t
QSP
is too short, TRIP can be activated.
•
The drive idles to standstill.
•
Controlled standstill is not possible.
•
Only stop category 0 can be reached.
•
Safe standstill is not possible, the safety door is not secured.
t
QSP
and the QSP ramp must always be adapted to the system being used.