Figure 69. M.2 backplane installation
After installing the M.2 backplane, complete the following steps:
1. Reinstall the PCIe riser-card if necessary (see “Install the PCIe riser-card assembly” on page 88).
2. Reinstall the LOM adapter if necessary (see “Install the LOM adapter” on page 72).
3. Reinstall the top cover (see “Install the top cover” on page 131).
4. Reconnect the power cords and any cables that you removed.
5. Install the server in the rack.
6. Power on the server and any peripheral devices.
Remove an M.2 drive from the M.2 backplane
Use this procedure to remove an M.2 drive from the M.2 backplane.
With M.2 backplane removed, complete the following steps to remove an M.2 drive from the M.2 backplane:
Step 1. Press both sides of the retainer and slide it backward to loosen the M.2 drive from the M.2
backplane.
Figure 70. M.2 drive removal
Note:
If your M.2 backplane has two M.2 drives, they will both release outward when you slide the
retainer backward.
.
Hardware replacement procedures
77
Содержание ThinkSystem SR850
Страница 1: ...ThinkSystem SR850 Maintenance Manual Machine Type 7X18 and 7X19 ...
Страница 8: ...vi ThinkSystem SR850 Maintenance Manual ...
Страница 58: ...50 ThinkSystem SR850 Maintenance Manual ...
Страница 142: ...134 ThinkSystem SR850 Maintenance Manual ...
Страница 166: ...158 ThinkSystem SR850 Maintenance Manual ...
Страница 170: ...162 ThinkSystem SR850 Maintenance Manual ...
Страница 174: ...Taiwan BSMI RoHS declaration 166 ThinkSystem SR850 Maintenance Manual ...
Страница 176: ...168 ThinkSystem SR850 Maintenance Manual ...
Страница 182: ...174 ThinkSystem SR850 Maintenance Manual ...
Страница 183: ......
Страница 184: ...Part Number SP47A24295 Printed in China 1P P N SP47A24295 1PSP47A24295 ...