The ThinkAgile VX5520 appliances are supported in the following environment:
Air temperature:
Operating:
ASHRAE Class A4: 5 °C - 45 °C (41 °F - 113 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 125-m (410-ft) increase
in altitude
ASHRAE Class A3: 5 °C - 40 °C (41 °F - 104 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 175-m (574-ft) increase
in altitude
ASHRAE Class A2: 10 °C - 35 °C (50 °F - 95 °F); for altitudes above 900 m (2,953 ft),
decrease the maximum ambient temperature by 1 °C for every 300-m (984-ft) increase
in altitude
Non-operating: 5 °C - 45 °C (41 °F - 113 °F)
Storage: -40 °C - +60 °C (-40 °F - 140 °F)
Maximum altitude: 3,050 m (10,000 ft)
Humidity:
Operating:
ASHRAE Class A4: 8% - 90% (non-condensing); maximum dew point: 24 °C (75 °F)
ASHRAE Class A3: 8% - 85% (non-condensing); maximum dew point: 24 °C (75 °F)
ASHRAE Class A2: 8% - 80% (non-condensing); maximum dew point: 21 °C (70 °F)
Storage: 8% - 90% (non-condensing)
Electrical:
100 - 127 (nominal) V AC; 50 Hz / 60 Hz (1100 W power supplies only)
200 - 240 (nominal) V AC; 50 Hz / 60 Hz
180 - 300 V DC (supported in China only)
Acoustics (maximum configuration, operating): 6.8 bels
Vibration:
Operating: 0.21 G rms at 5 Hz to 500 Hz for 15 minutes across 3 axes
Non-operating: 1.04 G rms at 2 Hz to 200 Hz for 15 minutes across 6 surfaces
Shock:
Operating: 15 G for 3 milliseconds in each direction (positive and negative X, Y, and Z axes)
Non-operating:
12 kg - 22 kg: 50 G for 152 in./sec velocity change across 6 surfaces
23 kg - 31 kg: 35 G for 152 in./sec velocity change across 6 surfaces
The following table lists the maximum system power load, rated inlet current, and system heat output
based on the power supply and source voltage.
Table 17. Rated system power, inlet current, and system heat output
Power supply
Source voltage
Maximum power
load per system
(two power supplies)
Rated current
per inlet
System
heat output
1100W AC Platinum
100 - 127 V AC
1382 W
12 A
4715 BTU/hour
200 - 240 V AC
1408 W
6 A
4804 BTU/hour
180 - 300 V DC
1408 W
5.1 A
4804 BTU/hour
1600W AC Platinum
200 - 240 V AC
2068 W
8.7 A
7056 BTU/hour
180 - 300 V DC
2024 W
7.3 A
6906 BTU/hour
Regulatory compliance
Lenovo ThinkAgile VX5520 Appliance
21