Figure 70. Installing the thermal sensor
4. Connect the thermal sensor cable to the thermal sensor connector on the system board. See “System
SD module
• “Removing the SD module” on page 78
• “Installing the SD module” on page 79
Removing the SD module
To remove the SD module, do the following:
1. Prepare your server. See “Preparing your server and removing the server cover” on page 41.
2. Lay the server on its side for easier operation.
3. Locate the SD module. See “Server components” on page 16.
4. Disconnect the SD module cable.
5. Remove the SD module from the SD module bracket.
Figure 71. Removing the SD module
6. Both sides of the SD module support the installation of an SD card. If any SD card is installed, remove
the card.
78
ThinkServer TS150 User Guide and Hardware Maintenance Manual