6 Commissioning
Operating system update
GEL 8251
25
Starting LingiMon with selected binary file (.h86)
The status bar provides information on the COM port (COM 2) selected, the trans-
mission rate (57600 Baud) as well as type of file loaded.
Prior to transmitting the data to the flash memory on the device, this memory is first
cleared. In general it is sufficient to clear only the operating system area – as per the
default in the program. Then any existing PLC program and the system parameter set-
tings will be retained. The other option can be enabled in the
Download options
(click
connector icon).
Do not switch to another application during the transmission of the data – the
transmission window must remain active, progress can then be followed using the
progress bar displayed. Otherwise Windows-specific errors can occur during the
transmission process that will result in the CompactController ceasing to respond.
In such a case repeat the transmission.
After confirming using OK, the program will prompt you to reset the device.
Switch off the CompactController.
Press the miniature button in the housing as per the following figure using a non-
metallic object (e.g. match) and switch the device back on.