background image

1

WARNING

Improper installation, adjustment, alteration, service or 

maintenance can cause property damage, personal injury 

or loss of life.  Installation and service must be performed 

by a qualified installer, service agency or the gas supplier

CAUTION

Danger of sharp metallic edges.  Can cause injury.

Take care when servicing unit to avoid accidental contact 

with sharp edges.

INSTALLATION INSTRUCTIONS FOR ECONOMIZERS 

USED WITH ZC,ZG,ZH 092-150 UNITS

Z1ECON16B-1 (11G98) ECONOMIZERS

HORIZONTAL ECONOMIZERS

!

!

Package 1 of 1 contains:

     1 - Economizer damper assembly

 

1 - Outdoor air damper

 

1 - Return air damper

 

1 - Gravity exhaust damper

 

1 - Horizontal blank-off panel

 

1 - Economizer actuator

 

1 - Economizer control module

 

1 - Outdoor air temperature sensor

     1 - Hardware bag

 

1 - Mixed air sensor

 

3 - #10-14 x 3/4” screws with washer

 

11 - #10-16 x 5/8” screws

     1 - Side economizer panel

     1 - Wiring diagram label

Order Of Installation

 Economizer

 

Mixed air sensor

 

Optional OA and RA sensors

 

Power Exhaust fans (optional)

 

Side economizer panel

Shipping and Packing List

Application

The Z1ECON16B-1 (11G98) economizer is used with 

ZC,ZG,ZH 092-150 units in horizontal air discharge 

applications.  Economizer dampers will modulate to maintain 

55

o

F (13

o

C) supply air when outdoor air is suitable.  The mixed 

air temperature sensor measures the supply air sensible 

temperature.
An outdoor air sensor is used to determine whether outdoor air 

is suitable for free cooling.  The outdoor air sensor is factory-

installed in all economizers.  Other outdoor and return air (OA 

and RA) sensor options are available to determine whether 

outdoor air is suitable for free cooling.  See Table 1 and the 

instructions provided with optional senors.

INDOOR AIR QUALITY SENSOR

An IAQ sensor is used when demand control ventilation (DCV) 

is specified.  Damper minimum position can be set lower than 

traditional minimum air requirements resulting in cost savings.  

The IAQ sensor allows the economizer control module to 

open dampers to traditional ventilation requirements as room 

occupancy (CO

2

) increases.

For proper operation, the IAQ sensor must provide a 2-10VDC, 

100 ohm impedance signal.  Connect sensor leads to AQ and 

AQ1 terminals on the economizer control module located in the 

filter section.

TABLE 1

Sensors

Dampers modulate to maintain

55

o

F mixed air (R1) when:

*Single OA Sensible

OA temperature is lower

than free cooling setpoint

Single OA Enthalpy

OA temperature and humidity is 

suitable for free cooling

Differential Enthalpy

- 1 in OA & 1 in RA

OA temperature and humidity is 

lower than RA temperature and 

humidity.

Figure 1

*Single OA sensible sensor is shipped standard on economizer

Cross Reference No. 507401-01

Содержание Z1ECON16B-1

Страница 1: ...n outdoor air is suitable The mixed air temperature sensor measures the supply air sensible temperature An outdoor air sensor is used to determine whether outdoor air is suitable for free cooling The...

Страница 2: ...ure 3 Economizer Control shown w o relief damper Blower access panel backside Economizer control module in shipping location Must be relocated to control box Economizer damper actuator Plug for option...

Страница 3: ...GND to ground Yel Cool 1 to Y1 and Blue Cool 2 to Y2 Disconnect the factory installed terminals at TB1 Y1 and Y2 Connect these terminals to control male terminal Y1 and Y2 3 Attach the control harness...

Страница 4: ...ing Demand Control Ventilation DCV Indoor IAQ is above set point requirement more fresh air Figure 8 Mixed Air Sensor Location Figure 7 Wiring Detail P142 TO P10 J10 J142 ECONOMIZER CONTROL MODULE RED...

Страница 5: ...hen outdoor air enthalpy is lower than 73o F and 50 RH If indoor air is too warm or humid lower the setpoint to B At setting B free cooling will be enabled at 70o F and 50 RH Differential Enthalpy Sen...

Страница 6: ...roximate desired fresh air percentage Use care when adjusting minimum potentiometer to avoid damaging potentiometer Note Damper minimum position can be set lower than traditional minimum air requireme...

Страница 7: ...etting for proper demand control ventilation Economizer Operation When the outdoor air is suitable dampers will modulate between minimum position and full open to maintain 55o F 12o C supply air See T...

Страница 8: ...MPER MECHANICAL COOLING UNOCCUPIED OCCUPIED1 OF Closed Closed No F Closed Minimum No Y1 Closed Minimum STAGE 1 Y2 Closed Minimum STAGE 1 IAQ sensor can open damper to DCV max 1 Damper position when no...

Отзывы: