Page 31
XP14 SERIES
Table 6. Normal Operating Pressures - 10 and Vapor +5 PSIG* (XP14-XXX-230-01 through 07)
IMPORTANT
Use table 8 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer
to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal
lations. Significant differences could mean that the system is not properly charged or that a problem exists with some
component in the system.
5
F (
5
C)**
XP14-018
XP14-024
XP14-030
XP14-036
XP14-042
XP14-048
XP14-060
Liquid / Vapor
Liquid / Vapor
Liquid / Vapor
Liquid/ Vapor
Liquid / Vapor
Liquid / Vapor
Liquid / Vapor
Heating
60 (15)
346 / 139
352 / 138
338 / 137
350 / 134
373 / 139
355 / 130
351 / 117
50 (10)
323 / 117
331 / 114
334 / 112
331 / 117
363 / 117
336 / 113
333 / 105
40 (4)
306 / 98
304 / 99
312 / 93
313 / 97
348 / 97
315 / 88
316 / 88
30 (-1)
278 / 84
299 / 80
302 / 74
298 / 83
336 / 74
296 / 72
308 / 70
20 (-7)
273 / 66
283 / 66
280 / 53
284 / 66
322 / 64
286 / 64
300 / 61
Cooling
65 (18)
226 / 140
233 / 137
238 / 138
220 / 138
223 / 125
231 / 136
243 / 136
70 (21)
244 / 141
252 / 138
263 / 139
236 / 140
241 / 130
248 / 139
263 / 137
75 (24)
263 / 142
271 / 140
279 / 139
256 / 141
261 / 134
271 / 140
282 / 138
80 (27)
283 / 143
292 / 141
299 / 140
276 / 142
282 / 138
291 / 142
306 / 139
85 (29)
302 / 144
314 / 142
324 / 141
298 / 143
302 / 139
312 / 143
327 / 140
90 (32)
328 / 145
338 / 143
340 / 142
321 / 144
326 / 140
335 / 144
351 / 141
95 (35)
351 / 146
361 / 145
375 / 145
344 / 144
349 / 141
359 / 145
376 / 142
100 (38)
376 / 147
387 / 146
397 / 145
369 / 146
374 / 142
384 / 146
401 / 143
105 (41)
402 / 148
412 / 147
424 / 147
394 / 147
399 / 143
411 / 148
426 / 145
110 (38)
430 / 149
441 / 148
454 / 150
421 / 148
428 / 145
439 / 149
452 / 146
115 (45)
465 / 150
471 / 151
485 / 150
449 / 149
455 / 146
468 / 150
484 / 148
*IMPORTANT—These are most popular match-up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.