19
ELECTRIC HEAT DATA
018-036
VVCA018H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Low
Medium
High
Volt
kW
1
Btuh
5 kW
V8EH0050P-1P (
13P59
) 208
3.8
12,800
3.0
26.8
30
•
•
•
220
4.2
14,300
3.0
27.8
30
•
•
•
230
4.6
15,700
3.0
28.8
30
•
•
•
240
5.0
17,100
3.0
29.8
30
•
•
•
7.5 kW
V8EH0080P-1P (
13P63
) 208
5.6
19,200
3.0
37.8
4
40
5
- - -
•
•
220
6.3
21,500
3.0
39.8
4
40
5
- - -
•
•
230
6.9
23,500
3.0
41.8
45
5
- - -
•
•
240
7.5
25,600
3.0
42.8
45
5
- - -
•
•
VVCA024H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Low
Medium
High
Volt
kW
1
Btuh
5 kW
V8EH0050P-1P (
13P59
) 208
3.8
12,800
3.0
26.8
30
•
•
•
220
4.2
14,300
3.0
27.8
30
•
•
•
230
4.6
15,700
3.0
28.8
30
•
•
•
240
5.0
17,100
3.0
29.8
30
•
•
•
7.5 kW
V8EH0080P-1P (
13P63
) 208
5.6
19,200
3.0
37.8
4
40
5
- - -
•
•
220
6.3
21,500
3.0
39.8
4
40
5
- - -
•
•
230
6.9
23,500
3.0
41.8
45
5
- - -
•
•
240
7.5
25,600
3.0
42.8
45
5
- - -
•
•
10 kW
V8EH0100P-1P (
13P64
) 208
7.5
25,600
3.0
48.8
4
50
5
- - -
•
•
220
8.4
28,700
3.0
51.8
60
5
- - -
•
•
230
9.2
31,400
3.0
53.8
60
5
- - -
•
•
240
10.0
34,100
3.0
55.8
60
5
- - -
•
•
VVCA030H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Volt
kW
1
Btuh
Low
Medium
High
5 kW
V8EH0050P-1P (
13P59
) 208
3.8
12,800
3.0
26.8
30
•
•
•
220
4.2
14,300
3.0
27.8
30
•
•
•
230
4.6
15,700
3.0
28.8
30
•
•
•
240
5.0
17,100
3.0
29.8
30
•
•
•
7.5 kW
V8EH0080P-1P (
13P63
) 208
5.6
19,200
3.0
37.8
4
40
5
- - -
•
•
220
6.3
21,500
3.0
39.8
45
5
- - -
•
•
230
6.9
23,500
3.0
41.8
45
5
- - -
•
•
240
7.5
25,600
3.0
42.8
45
5
- - -
•
•
10 kW
V8EH0100P-1P (
13P64
) 208
7.5
25,600
3.0
48.8
4
50
5
- - -
•
•
220
8.4
28,700
3.0
51.8
60
5
- - -
•
•
230
9.2
31,400
3.0
53.8
60
5
- - -
•
•
240
10.0
34,100
3.0
55.8
60
5
- - -
•
•
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold text indicates that the circuit breaker on CB” circuit breaker models must be replaced with size noted. See Table on page <OV>.
5
Do not operate fan on low speed when V8EH Electric Heat Kit is used with VVCA air handler.