–10–
4. Auto Operation (Cooling Model only)
The operation procedure is as following.
Auto Operation for Cooling
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation Condition
Intake-air Temperature
Setting temperature
Fan speed
Over 26°C
25°C
Over 24°C~below 25.5°C
Intake air -1.0°C
Over 22°C~below 23.5°C
Intake air -0.5°C
below 21.5°C
Intake air Temperature(18°C, MAX)
When Switch to
Auto Operation
Controlled
by Fuzzy logic
Intake Air Temp.
Indoor Fan Speed
Compressor
ON
OFF
Fuzzy Speed
ON
OFF
Setting Temp. +1
°
C
(Compressor ON)
Setting Temp. -1
°
C
(Compressor OFF)
3 minutes
More than
3 minutes
More than