7

Figure 3. Mounting Bracket Positioning

Model

A

B

VCFA012-024

19-7/8” (505 mm)

19-7/8” (506 mm)

VCFA030

31-1/4” (795 mm)

19-7/8” (506 mm)

VCFA036-048

42-1/8” (1070 mm)

17-3/4” (450 mm)

VCFA054

42-1/8” (1070 mm) 15” (380 mm)

 

A

B

4.  The unit should be installed high enough for a gravity 

drain to function properly. If necessary, a 

fi

 eld provided 

external pump can be installed at the unit. See 

fi

 gure 1 

for pipe connection locations.

5. Upon con

fi

 rming the two brackets are level, correctly 

spaced and secured to the wall; lift the unit onto the 
brackets. Con

fi

 rm the unit is level before continuing.

Ceiling Installation

1.  Remove the side panel and the grille. See 

fi

 gure  4.

NOTE - Do not remove the grille on VCFA048 or 054 
models.

Grille*

Side panel

Figure 4. Remove Side Panel and Grille

*Do Not 
remove grille 
on VCFA048 
or 054 units

2.  Install four factory-provided mounting bolts by screwing 

them into the provided threaded holes in the unit body. 
See 

fi

 gure 7 for mounting bolt installation locations. The 

bolts should only extend from the body a distance which 
enables the bracket to engage the bolts and secure the 
unit. 

3.  Make sure that the structural ceiling is able to support 

the weight of the unit. It may be necessary to add 
support.

4. 

Install suspension rods in the structural 
ceiling or concrete slab in a suitable location. 
If the structural ceiling is constructed of concrete, install 
anchors to accept four suitably sized threaded rods to 
suspend the indoor unit. If the structural ceiling includes 
wooden joists, use angle iron or Unistrut channel 

fi

 xed 

securely in place to accept the threaded rods. 

NOTE - 

Threaded rod (requirement of Lennox warranty program) 
is the ONLY acceptable method of suspending the unit; 
do not use chains or straps. See 

fi

 gure 5.

5.  Slide one nut and one washer onto each threaded rod. 

Use electrical tape to keep the washer from falling off. 
Position the nuts slightly above the 

fi

 nal resting place of 

the suspension brackets. 

Figure 5. Locate Threaded Rods

Threaded rod

Field-provided 
isolation grommet

Washer

Leveling nut

Suspension 

bracket

Figure 6. Locate Suspension Bracket on Threaded Rod

6. VCFA012-048 units:

  A

fi

 x the two long suspension 

brackets provided in accessory package to the 
previously installed threaded rods. See 

fi

 gure  6. 

VCFA054 units: 

A

fi

 

x the four short suspension 

brackets  to the unit body. See 

fi

 gure  7. 

Install the VCFA054 unit directly onto  the threaded rods 
as instructed in step 8 and then proceed to step 6. Step 
9 will not apply to VCFA054 installation. 

7.  Slide a washer and then a nut onto each rod below 

each suspension bracket. Use the leveling nut (beneath 
suspension brackets) to adjust the bracket to the correct 
height. Remove the electrical tape holding the upper 
washers and nuts in place and tighten each of the four 
nuts above the brackets down onto the brackets. This 
will ensure that the unit remains level. See 

fi

 gure 6.

Anchor

CONCRETE CEILING

USING ANCHORS

ANGLE IRON

ACROSS 

WOODEN JOISTS

Threaded rod

Angle iron bolted in 

place across wooden 

joists

Wooden joist

Threaded rod

Содержание VCFA012S4

Страница 1: ...ions are intended as a general guide and do not supersede local codes in any way Consult authorities having jurisdiction before installation WARNING Improper installation adjustment alteration service...

Страница 2: ...036 36 000 Btuh 048 48 000 Btuh 054 54 000 Btuh Voltage P 208 230V 1 phase 60hz System Piping CAUTION VRF system piping is customized for each installation The LVSS piping report is an engineered desi...

Страница 3: ...SIDE VIEW 3 7 8 97 2 1 2 64 MOUNTING HOLES 4 DRAIN OUTLET Either Side DRAIN OUTLET Rear 50 3 8 1280 47 1195 21 1 2 547 20 1 4 515 8 1 8 207 1 1 2 38 1 5 8 41 26 660 7 7 8 200 7 1 8 181 5 1 4 134 3 7 8...

Страница 4: ...8 185 5 3 4 146 MOUNTING HOLES 4 DRAIN OUTLET Either Side VCFA036S4 VCFA048S4 FRESH AIR INTAKE 4 105 dia REAR VIEW SIDE VIEW BOTTOM VIEW 65 3 4 1670 65 1 2 1613 42 1 8 1070 LIQUID LINE SUCTION LINE 1...

Страница 5: ...VIEW SIDE VIEW SIDE VIEW SUPPLY AIR SUPPLY AIR 24 610 Service Clearance Front of Unit DROP CEILING 3 4 19 WALL WALL CEILING APPLICATIONS CEILING AND FLOOR APPLICATIONS FLOOR APPLICATIONS Unit Flush wi...

Страница 6: ...formance horizontal installation only Ensure the structural wall floor or ceiling can support the weight of the unit Installation Floor Wall Applications 1 Locate a suitable position within the space...

Страница 7: ...aded rods to suspend the indoor unit If the structural ceiling includes wooden joists use angle iron or Unistrut channel fixed securely in place to accept the threaded rods NOTE Threaded rod requireme...

Страница 8: ...connected to the indoor unit Table 1 lists the connection sizes at the indoor unit The connections are made using the provided brass flare nuts at the end of the refrigerant piping connections Both l...

Страница 9: ...ion Outside Diameter Recommended Torque No torque wrench available Finger tighten and use an appropriately sized wrench to turn an additional Inches U S 1 4 15 ft lb 1 4 turn 3 8 26 ft lb 1 2 turn 1 2...

Страница 10: ...ain etc to ensure that the line will drain freely 4 After the system installation is complete the condensate drain line must be checked for leaks and proper drainage If a field provided condensate pum...

Страница 11: ...over tightened screws might be damaged Refer to the table below for the tightening torque of the terminal screws A disconnection device having an air gap contact separation in all active conductors s...

Страница 12: ...L1 L2 L3 L1 L2 L1 L2 Single Phase power wiring PQE PQE Indoor units and MS boxes on the same refrigeration circuit should have a common power supply but must have an independent disconnect switch inst...

Страница 13: ...13 Figure 13 Typical Communication Wiring Diagram VRF Heat Recovery System NOTE Each communication wire from the MS box should follow the refrigerant piping for that port...

Страница 14: ...7 21 5 1 3 6 86 7 21 8 725 6 POWER IN 208 230V 1 PHASE 60 hz Figure 14 VCFA012 48S4 1 Wiring Diagram Figure 15 VCFA054S4 1 Wiring Diagram 1 1 75 7 7 7 7 6 6 6 6 1 21 21 21 21 1 1 1 1 9 1 1 7 1 2 6 3...

Страница 15: ...OCK EVAP OUTLET TEMP IN COOLING MODE PLUG JACK LEVEL SWING MOTOR GND CN30 FAN CTON HTON AUXH HHE interface Current range 0 1A Voltage range 0 AC DC24V L1 L2 GROUND GMA GMB EEV T2B T2 TR XS1 11 XP1 11...

Страница 16: ...e Air Knockout Outside Air Knockout 1 Knock out the outside air supply opening See figure 18 2 Remove any insulation 3 Connect the outside air duct to cassette body using the four screw holes shown in...

Отзывы: