56
Set Room Temperature Sensor Calibration
If the indoor temperature displayed on the controller differs from the actual indoor temperature,
use this screen to calibrate the sensor. The controller will add the value selected to the sensed
temperature as selected on the sensor location screen. The correction ranges from -4°F to 4°F (or
-2°C to 2°C).
1. Tap the Menu button on the Home screen.
2. Tap the Service button and then enter your password.
3. Tap the Room Temperature Sensor Calibration button.
4. Drag the round slider or tap the Increase or Decrease button to adjust and select the correc-
tion for indoor temperature sensor as required.
5. Tap the Save button to save the settings.
Figure 61. Set Room Temperature Sensor Calibration