background image

 

@DNOVA THS_R410A-IOM-1304-E

 

18

 

Maintenance 

 

The only operations to be performed by the user are to switch the unit On and Off. 
All other operations are to be considered maintenance work and must thus be carried out by qualified personnel trained 
to do their job in accordance with current laws and regulations. 

 

8.1 

Warnings 

 

 

All the operations described in this chapter MUST ALWAYS BE PERFORMED BY QUALIFIED  

 

PERSONNEL ONLY. 

 

 

Before carrying out any work on the unit or accessing internal parts, make sure you have 

 

disconnected it from the mains electricity supply. 

 

 

The upper part and the outlet pipe of the compressor reach high temperatures. Be especially 

 

careful when working in the surrounding area with the panels off. 

 

 

Be especially careful when working in proximity to finned coils since the 0.11 mm thick aluminium 

 

fins can cause superficial injuries due to cuts. 

 

 

After completing maintenance jobs, always replace the panels enclosing the units and secure them 

 

with the fastening screws provided. 

 

 

8.2 

Periodical checks 

 

To guarantee a constantly satisfactory performance over time, it is advisable to carry out routine maintenance and 
checks as described below. The indications below are related to standard tear and wear. 
 

Tab. 6 

Periodical checks 

 

Operation 

Frequency 

Check the efficiency of all the control and safety devices. 

Once a year 

Check the terminals on the electric control board and compressor terminal boards to ensure that they are 
securely tightened. The movable and fixed contacts of the circuit breakers must be periodically cleaned and 
replaced whenever they show signs of deterioration. 

Once a year 

Check the refrigerant level by means of the liquid level indicator. 

Every 6 mos. 

Check the efficiency of the differential air pressure switch and dirty filter differential pressure switch. 

Every 6 mos. 

Check the condition of the air filter and replace it if necessary. 

Every 6 mos. 

Check the humidity indicator (

green

 = dry, 

yellow

 = humid) on the liquid level indicator; if the indicator is not 

green as shown on the indicator sticker, replace the filter. 

Every 6 mos. 

 

Содержание THS310

Страница 1: ...www lennoxemea com INSTALLATION OPERATING AND MAINTENANCE CEILING MOUNTED SPLIT UNIT DNOVA THS 2 5 38 kW ADNOVA THS_R410A IOM 1304 E...

Страница 2: ......

Страница 3: ...of the unit 10 4 3 Evacuating a circuit contaminated with refrigerant 11 4 4 Charging positions single point 11 5 Electrical Connections 12 5 1 Generalities 12 6 Starting Up 14 6 1 Preliminary checks...

Страница 4: ...7 0 C 45 0 C 44 0 C 45 C 47 C Temp Humidity conditions Min 19 C 30 R H Max 35 C 50 R H Storage conditions Min 10 C 90 R H Max 55 C 90 R H 1 3 Cooling circuit The entire cooling circuit is built in the...

Страница 5: ...m Alarm signalling Display of operating parameters RS232 RS485 serial output management optional Phase sequence error Not displayed by the mP but prevents the compressor from starting up See microproc...

Страница 6: ...P 4 Evaporator 9 Condensing pressure probe 5 Filter dryer 10 Tap THS045 056 073 090 105 120 145 310 380 Pos Description Pos Description 1 Compressor 8 High pressure switch HP 2 Condenser 9 Condensing...

Страница 7: ...of electrical components may cause hazardous situations during installation and maintenance work All work on the unit must be carried out by qualified personnel only trained to do their job in accord...

Страница 8: ...taken to avoid abrupt or violent maneuvers The unit must be handled carefully and gently avoid using machine components as anchorages or holds and always keep it in an upright position The unit should...

Страница 9: ...when choosing the best site for installing the unit and the relative connections position of the indoor unit next to the main heat source location of power supply solidity of the supporting ceiling wa...

Страница 10: ...lows In both cases the holes in the ceiling wall have to be protected by rainproof grilles with pre filter to avoid water or foreign bodies get in the conditioner Outside air taken into the room by th...

Страница 11: ...number of pre shaped bends if this is not possible every bend must have a radius of at least 100mm The gas line must be insulated The liquid line must be kept far from heat sources if this is not poss...

Страница 12: ...with ambient air further evaporation of remaining liquid the original pressure in the tank will be restored after a certain period of time Fig 3 Gibb s law diagram 4 2 Full vacuum and charge of the u...

Страница 13: ...d this sensitive sensor and misinterpret the value for a certain period of time For this reason if no machine for recovering refrigerant is available it is nonetheless advisable to switch on the crank...

Страница 14: ...luctuations exceeding 5 and the unbalance between phases must always be below 2 The above operating conditions must always be complied with failure to ensure said conditions will result in the immedia...

Страница 15: ...DNOVA THS_R410A IOM 1304 E 13 Legend 1 Power supply for internal unit THSI 2 Power supply for external unit THSC 3 Auxiliary cables MAIN ELECTRICAL PANEL 2 1 3...

Страница 16: ...n the sump and limit the quantity of refrigerant dissolved in it To verify whether the heating elements are working properly check the lower part of the compressors it should be warm or in any case at...

Страница 17: ...ors In next mask m_on_off that you can see pushing Down it is possibile to turn the unit on or off pushing Enter Down and then again Enter It is also shown if the unit is a master or a slave unit this...

Страница 18: ...eter placed on the compressor intake pipe 2 read the temperature indicated on the scale of a pressure gauge likewise connected to the intake side refer to the pressure gauge scale for the refrigerant...

Страница 19: ...50 30 Differential air pressure switch dirty filter Pa 50 20 Values to be calibrated depending on the application Tab 5 Setting of safety control devices Control device Activation Differential Resetti...

Страница 20: ...ng the units and secure them with the fastening screws provided 8 2 Periodical checks To guarantee a constantly satisfactory performance over time it is advisable to carry out routine maintenance and...

Страница 21: ...nd air filter compartment Remove the damper fastening screws placed at the side Pull out the entire damper section to access the servomotor Grilled panel Servomotor Remove the grilled panel to access...

Страница 22: ...st empty out the circuit before repairing the leaks with suitable alloys Do not use oxygen in the place of nitrogen as a test agent since this would cause a risk of explosion 8 5 Hard vacuum and dryin...

Страница 23: ...arged with nitrogen in the factory must not be charged with R22 or other refrigerants without the written authorization Lennox 8 7 Environmental protection The law implementing the regulations reg EEC...

Страница 24: ...cooling values exceeding 5 C Drain and pressurise the circuit and check for leaks Evacuate slowly for more than 3 hours until reaching a pressure of 0 1 Pa and then recharge in the liquid phase Unit...

Страница 25: ......

Страница 26: ...LENNOX DISTRIBUTION 33 4 72 23 20 20 www lennoxemea com ADNOVA THS_R410A IOM 1304 E Due to LENNOX EMEA ongoing commitment to quality the specifications ratings and dimensions are subject to change wit...

Отзывы: