IOM / TELECOOL THN - 0104 - E Page 15
SETTING OPERATING PARAMETERS
SETTING OPERATING PARAMETERS
GENERALITIES
All the control devices are set and tested in the factory
before the unit is dispatched. However, after the unit
has been in service for a reasonable period of time you
can perform a check on the operating and safety
devices. The settings are shown in Tables II and III.
All servicing of the equipment is to be considered
extraordinary maintenance and may be carried out BY
QUALIFIED TECHNICIANS ONLY: incorrect settings
may cause serious damage to the unit and injuries to
persons.
The operating parameters and control system settings
configurable by means of the microprocessor control are
password protected if they have a potential impact on
the integrity of the unit.
TABLE II - SETTING OF CONTROL DEVICES
CONTROL DEVICE
Differential air pressure switch (outlet air flow)
Differential air pressure switch (dirty filter)
Pa
Pa
SET POINT
50
50
DIFFERENTIAL
30
20
CONTROL DEVICE
Maximum pressure switch
Minimum pressure switch
Modulating condensation control device
Time lapse between two compressor starts
Bars-r
Bars-r
Bars-r
s
ACTIVATION
28.0
2
14
480
DIFFERENTIAL
4
1.5
7
-
RESETTING
Manual
Automatic
-