![Lennox T?CLASS TAA SERIES Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/lennox/t-class-taa-series/t-class-taa-series_installation-instructions-manual_1877089013.webp)
Page 13
TAA SERIES
Pulley Alignment
BELT
BLOWER
PULLEY
MOTOR
PULLEY
NOT ALIGNED
ALIGNED
AFTER ANY PULLEY ADJUSTMENT OR CHANGE OUT, PULLEYS
SHOULD BE ALIGNED WITH THE TENSIONER AS SHOWN.
TENSIONER
Figure 8. Typical Pulley Alignment
Air Volume Adjustment
FIXED
PULLEY
BLOWER
BELT
ADJUSTABLE
PULLEY
ADJUSTABLE PULLEY
ALLEN SCREW
RUN THE BLOWER WITHOUT A COOLING DEMAND.
USE THE STATIC PRESSURE AND REV/MIN READINGS TO DETERMINE
THE UNIT’S AIR VOLUME (SEE APPLICABLE BLOWER PERFORMANCE
TABLES).
MEASURE THE INDOOR BLOWER MOTOR’S RPM.
MEASURE THE STATIC PRESSURE EXTERNAL TO THE UNIT.
NOTE THE INDOOR COIL MUST BE DRY AND THE AIR
FILTERS MUST BE IN PLACE WHEN THE FOLLOWING
MEASUREMENTS ARE TAKEN.
LOOSEN THE ALLEN SCREW ON THE ADJUSTABLE PULLEY.
TURN THE ADJUSTABLE SHEAVE CLOCKWISE TO INCREASE THE AIR
VOLUME OR COUNTERCLOCKWISE TO DECREASE THE AIR VOLUME.
ONCE THE DESIRED AIR VOLUME HAS BEEN ACHIEVED, TIGHTEN THE
ALLEN SCREW.
1
2
3
4
5
6
7
Figure 9. Typical Air Volume Adjustment Procedure