SPB − 3 to 5 Ton R−410A Heat Pump

 

Outdoor Units 

/ Page 10

ARI RATINGS 

ARI Standard 210/240 Ratings

Capacity − Btuh

Efficiency

Total Watts

COP

I d

U it M d l N

Expansion

Cooling

High

Temp

Low

Temp

HSPF

Cool

High Low High Low

Indoor Unit Model No.

Expansion
Device

Cooling Temp.

Heating

Temp.

Heating SEER EER

IV

V

Cool

High

Heat

Low

Heat

High

Heat

Low

Heat

SPB036H4

3 TON

Air Handlers

Air Handlers

34,600 33,000 20,000 14.70 11.20 8.00 6.70 3080 2980 2550 3.24 2.30

CBX32M−030 (Multi−Position)

Factory TXV

34,800 33,000 19,900 15.00 11.20 8.00 6.70 3065 2975 2540 3.26 2.30

CB30U−31 (Up−Flow)

49L24

34,800 33,600 20,400 13.80 10.80 7.95 6.90 3200 3045 2640 3.24 2.26

3

 CB29M−46 (Multi−Position)

Factory TXV

34,800 33,600 20,600 13.80 10.50 7.70 6.75 3285 3210 2740 3.06 2.20

3

 CB29M−51 (Multi−Position)

Factory TXV

35,200 33,000 19,900 15.50 11.50 8.00 7.00 3055 2900 2495 3.34 2.34

CBX32MV−024/030 (Multi−Position)

Factory TXV

35,200 33,200 20,000 14.70 11.20 8.00 7.00 3105 2950 2550 3.30 2.30

CBX32M−036 (Multi−Position)

Factory TXV

35,400 33,400 20,200 14.50 11.20 8.00 6.70 3125 2950 2570 3.32 2.30

CB30U−41/46 (Up−Flow)

49L24

35,600 33,200 19,900 16.00 11.70 8.20 7.00 3045 2865 2480 3.40 2.34

4,5 

CBX32MV−036 (Multi−Position)

Factory TXV

35,600 33,000 19,700 15.70 11.70 8.20 7.00 3000 2835 2440 3.42 2.36

CBX27UH−036 (Up−Flow/Horizontal)

49L24

35,600 33,600 20,400 14.70 11.20 8.20 7.20 3110 2895 2470 3.40 2.42 CBX26UH−030 (Up−Flow / Horizontal)

Factory TXV

36,000 33,600 20,400 14.50 11.50 8.20 7.20 3110 2865 2455 3.44 2.44 CBX26UH−036 (Up−Flow / Horizontal)

Factory TXV

36,800 32,800 19,700 16.20 12.20 8.20 7.20 2970 2805 2385 3.42 2.42

CBX27UH−042 (Up−Flow/Horizontal)

49L24

Up−Flow Indoor Coils

Up−Flow Coils

35,200 33,800 20,600 14.00 11.00 8.00 7.00 3190 2995 2565 3.30 2.36

CX34−38A/B−6F

Factory TXV

Up−Flow Indoor Coils + Furnaces

Up−Flow Coils + Furnaces

35,600 33,600 20,400 15.20 11.20 8.20 7.00 3125 2915 2490 3.38 2.40 CX34−38A−6F

G60UHV−36A−070

Factory TXV

35,600 33,600 20,400 15.20 11.20 8.20 7.00 3145 2930 2505 3.36 2.38 CX34−38B−6F

G61MPV−36B−045

Factory TXV

35,600 33,400 20,200 15.20 11.50 8.20 7.00 3100 2910 2475 3.36 2.38 CX34−38B−6F

G61MPV−36B−070

Factory TXV

35,800 33,200 20,000 15.70 11.70 8.20 7.20 3040 2830 2405 3.44 2.44 CX34−38B−6F

G60UHV−36B−090

Factory TXV

36,200 32,200 19,500 16.00 11.70 7.70 6.70 3035 3075 2580 3.06 2.22 C33−44C

G61MPV−36C−090

49L24

36,400 32,000 19,400 16.00 12.00 7.70 6.70 3000 3080 2560 3.04 2.22 CX34−43C−6F

G61MPV−36C−090

49L24

36,400 32,200 19,500 16.00 11.70 7.70 6.70 3040 3095 2585 3.04 2.20 CX34−43B−6F

G60UHV−36B−090

49L24

Down−Flow Indoor Coils

Down−Flow Coils

34,800 33,400 20,400 13.70 10.90 7.70 6.70 3190 3065 2610 3.20 2.28

CR33−48B/C−F

49L24

35,800 34,000 20,600 14.20 11.20 8.20 7.00 3195 2950 2555 3.38 2.36

CR33−50/60C−F

49L24

Down−Flow Indoor Coils + Furnaces

Down−Flow Coils + Furnaces

35,200 33,200 20,200 15.20 11.20 8.00 7.00 3100 2980 2520 3.26 2.34 CR33−48B−F

G61MPV−36B−070

49L24

35,200 33,400 20,200 15.20 11.20 8.00 7.00 3140 2995 2550 3.26 2.32 CR33−48B−F

G61MPV−36B−045

49L24

35,400 32,800 19,800 15.70 11.70 8.00 7.00 3000 2885 2425 3.34 2.40 CR33−48C−F

G61MPV−36C−090

49L24

35,400 32,800 19,900 15.50 11.50 8.00 7.00 3015 2890 2435 3.32 2.40 CR33−48B−F

G60DFV−36B−090

49L24

36,400 33,200 20,000 16.00 12.00 8.50 7.20 3005 2765 2370 3.52 2.48 CR33−50/60C−F

G61MPV−36C−090

49L24

Horizontal Indoor Coils

Horizontal Coils

34,800 33,600 20,400 13.70 10.95 7.70 6.70 3185 3045 2595 3.24 2.30

CH23−51

49L24

35,200 33,800 20,600 14.00 11.00 8.00 7.00 3190 2980 2555 3.32 2.36

CH23−65

49L24

Horizontal Indoor Coils + Furnaces

Horizontal Coils + Furnaces

35,800 32,200 19,500 15.70 11.70 7.70 6.70 3035 3105 2590 3.04 2.20 CH33−42B−2F

G60UHV−36B−090

49L24

36,200 32,000 19,400 16.00 12.00 7.70 6.70 3000 3085 2565 3.04 2.22 CH33−48C−2F

G61MPV−36C−090

49L24

36,200 32,200 19,500 16.00 11.70 7.70 6.70 3040 3075 2585 3.06 2.20 CH33−44/48B−2F

G60UHV−36B−090

49L24

NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).

1

Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;

Cooling Ratings − 

95

_

F outdoor air temperature and 80

_

F db/67

_

F wb entering indoor coil air.

High Temperature Heating Ratings − 

47

_

F db/43

_

F wb outdoor air temperature and 70

_

F db entering indoor coil air.

Low Temperature Heating Ratings − 

17

_

F db/15

_

F wb outdoor air temperature and 70

_

F db entering indoor coil air.

2

Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).

3

Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (

58M81

) is recommend for field installation.

4

Blower control must be set for a time−off blower delay.

5

Most popular air handler combination.

Содержание SPB036H4

Страница 1: ...NUMBER IDENTIFICATION s P B Y 1 036 H 4 4 S Major Design Sequence A 1st Generation B 2nd Generation Brand Family S T Classt Product Line Unit Type P Heat Pump Outdoor Unit Nominal Cooling Capacity To...

Страница 2: ...ers or add on indoor coils with FM21 dual fuel furnace control See FM21 bulletin Controls section Also see Indoor Coils and Air Handlers sections for indoor unit data Units shipped completely factory...

Страница 3: ...See Specifications table for selection Not available for 060 model and must be field fabricated COMPRESSOR Copeland Scroll Ultra Techt Two Stage Compressor Compressor features high efficiency with uni...

Страница 4: ...t Refrigerant line connections and field wiring inlets are located in one central area of the cabinet See dimension drawing CONTROLS Defrost Control Solid state control furnished as standard Gives a d...

Страница 5: ...1 Accessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1...

Страница 6: ...17 62 Locked rotor amps 58 88 135 Power factor 0 99 0 99 0 99 Outdoor Coil Fan Motor Full load amps 1 1 1 7 1 8 Fan Motor Locked rotor amps 2 1 3 1 2 9 OPTIONAL ACCESSORIES must be ordered extra Comp...

Страница 7: ...036H4 80 5 70 5 71 5 71 0 68 5 63 5 58 5 53 5 76 SPB048H4 81 0 72 5 71 5 73 0 70 5 66 0 60 5 58 5 76 SPB060H4 80 5 72 5 73 5 77 5 72 5 67 0 62 5 58 5 78 NOTE the octave sound power data does not inclu...

Страница 8: ...POR LINE CONNECTION LIQUID LINE CONNECTION UNIT SUPPORT FEET 8 1 2 216 SPB036H4 T0 SPB048H4 BASE SECTION 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 UNIT SUPPORT FEET SPB060H4 BASE SECTION 16 7...

Страница 9: ...2 CX34 18 24B 6F C33 24B 2 CX34 18 24C 6F C33 24C 2 CX34 19A 6F C33 19A 2 CX34 25A 6F C33 25A 2 CX34 25B 6F C33 25B 2 CX34 30A 6F C33 30A 2 CX34 30B 6F C33 30B 2 CX34 30C 6F C33 30C 2 CX34 31A 6F C33...

Страница 10: ...4 G61MPV 36C 090 2 49L24 36 400 32 000 19 400 16 00 12 00 7 70 6 70 3000 3080 2560 3 04 2 22 CX34 43C 6F 4 G61MPV 36C 090 2 49L24 36 400 32 200 19 500 16 00 11 70 7 70 6 70 3040 3095 2585 3 04 2 20 C...

Страница 11: ...62D 6F 4 G60UHV 60D 135 Factory TXV 48 000 44 000 26 200 15 70 11 70 7 70 6 70 4090 4150 3510 3 10 2 18 CX34 60D 6F 4 G61MPV 60D 135 Factory TXV 48 500 44 000 26 400 15 70 11 70 7 70 6 70 4130 4110 34...

Страница 12: ...4 G60UHV 60D 135 Factory TXV 58 500 52 500 33 800 15 20 11 00 8 00 7 00 5270 5105 4510 3 02 2 20 CX34 62C 6F 4 G61MPV 60C 090 Factory TXV Down Flow Indoor Coils Down Flow Coils 55 500 53 000 33 800 1...

Страница 13: ...prietary products and recommended installation Retain Reference Article when specifying products and installation by an industry reference standard If retained list standard s referenced in this secti...

Страница 14: ...location in assembly d Field wiring diagrams e Dimensions internal and external construction details installation clearances recommended method of installation sizes and location of mounting boltholes...

Страница 15: ...rs to remain in place until installation Specifier Note Include or remove following section as project dictates E Waste Management and Disposal Specifier Note ENVIRONMENT The disposal of packaging was...

Страница 16: ...inted base section d Compressor and control box 1 Located in separate compartment inside unit 2 Insulated with thick fiberglass insulation e Control box with controls factory wired f Large removable s...

Страница 17: ...truction 4 Lanced ripple edged aluminum fins 5 Coil is leak tested at factory e Entire coil to be accessible for cleaning Standard factory installed features 1 Expansion valve to be factory piped 2 Di...

Страница 18: ...r s written data including product technical bulletins product catalog installation instructions and product carton installation instructions PART 3 02 EXAMINATION A Site Verification of Conditions Ve...

Страница 19: ...SIONS Sections Description of Change Dimensions Added new base section view Specifications Table Refrigerant charge changed on SPB036H4 and SPB060H4 models Guide Specifications Added Guide Specificati...

Страница 20: ...tment to quality Specifications Ratings and Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pro...

Отзывы: