Page 12
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 2. As an alternate,
use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materials. Use
transition solvent cement when bonding ABS to either PVC or CPVC. Low temperature solvent cement is recommended.
Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC.
TABLE 3
OUTDOOR TERMINATION USAGE*
Input Size
Vent Pipe
Dia. in.
STANDARD
CONCENTRIC
Flush
Mount Kit
Wall Kit
Wall Ring
Kit
Field
Fabricated
1-1.2 inch
2 inch
3 inch
2 inch
3 inch
2 inch
71M80
(US)
4
44W92
(CA)
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
51W11
(US)
51W12
(CA)
22G44
(US)
4
30G28
(CA)
44J40
(US)
4
81J20
(CA)
15F74
045
2
3
YES
YES
1
YES
1
YES
5
YES
2
YES
2-1/2
3
YES
YES
1
YES
1
YES
5
YES
2
YES
3
3
YES
YES
1
YES
1
YES
5
YES
2
YES
070
2
3
YES
YES
1
YES
1
YES
5
YES
2
YES
2-1/2
3
YES
YES
1
YES
1
YES
5
YES
2
YES
3
3
YES
YES
1
YES
1
YES
5
YES
2
YES
090
2
3
YES
YES
YES
5
YES
YES
YES
2-1/2
3
YES
YES
YES
5
YES
YES
YES
3
3
YES
YES
YES
5
YES
YES
YES
110
2
YES
YES
YES
5
YES
YES
YES
2-1/2
YES
YES
5
YES
YES
YES
3
YES
YES
5
YES
YES
YES
135
3
YES
YES
5
YES
YES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total
vent length calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
1Requires field-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.
5 See table 7 for vent accelerator requirements.
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
NOTE -
A sheet metal screw may be used to secure the
intake pipe to the connector, if desired. Use a drill or self
tapping screw to make a pilot hole.
DANGER
Fumes from PVC glue may ignite during system check.
Allow fumes to dissipate for at least 5 minutes before
placing unit into operation.
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any
ridges or rough edges. If end is not chamfered,
edge of pipe may remove cement from fitting socket
and result in a leaking joint.
NOTE - Check the inside of vent pipe thoroughly for any
obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 -
Test fit joint and mark depth of fitting on outside of
pipe.
5 - Uniformly apply a liberal coat of PVC primer for
PVC or use a clean dry cloth for ABS to clean inside
socket surface of fitting and male end of pipe to
depth of fitting socket.
6 - Promptly apply solvent cement to end of pipe and
inside socket surface of fitting. Cement should be
applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply
second coat to end of pipe.
NOTE -
Time is critical at this stage. Do not allow prim
-
er to dry before applying cement.