background image

Page 46

Field Wiring Applications With Conventional Thermostat (Continued)

Thermostat

DIP Switch Settings and On-Board Links (figure 4)

Wiring Connections

DIP Switch 1

Thermostat

Heating

Stages

On Board Links Must Be Cut To Select

System Options

Dual Fuel
Single Stage
Heat Pump

ComfortSense
thermostat w/
dual fuel capa­
bilities
Capable of 2
stage gas heat
control

OFF

CUT ON-BOARD LINK

W951
HEAT

PUMP

L7742U
T'STAT

FURNACE

TERM. STRIP

HEAT PUMP

67M41*

Y

H

L

Y2

D

B

L

Y2

T

T

outdoor

sensor

Dual Fuel
Two Stage
Heat Pump

ComfortSense
thermostat w/
dual fuel capa­
bilities
Capable of 2
stage gas heat
control

OFF

CUT ON-BOARD LINK

W951
HEAT

PUMP

CUT ON-BOARD LINK

W915

2 STAGE

COMPR

FURNACE

TERM. STRIP

HEAT PUMP

out blue

67M41*

H

L

Y2

D

B

L

Y2

T

T

outdoor
sensor

L7742U
T'STAT

*  Connect W1 to W1 ONLY if using defrost tempering kit 67M41

NOTE - 

Do NOT

 make a wire connection between the room thermostat L terminal and the L terminal of the SL280

integrated control.

Содержание SL280UH060NV36A

Страница 1: ...res outlined in this manual are presented as a recom mendation only and do not supersede or replace local or state codes In the absence of local or state codes the guidelines and procedures outlined i...

Страница 2: ...according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Model No SL280UH080NV60C SL280UH100NV60C 1 AFUE 80 80 High F...

Страница 3: ...Exchanger Combustion Air Inducer Gas Valve Intake Air Elbow Access Panel Inner Access Panel Intake Screen Blower Assem Power Choke 4 and 5 Ton Only Control Box includes integrated control interlock sw...

Страница 4: ...ace entire control Can cause injury or death Unsafe operation will re sult if repair is attempted 4 Integrated Control A92 Units are equipped with the communicating enabled Sur eLight two stage variab...

Страница 5: ...ermostat Move the DIP switch to ON for use with a single stage thermostat While in the single stage thermostat mode the burners will always fire on first stage heat The combustion air inducer will ope...

Страница 6: ...STAGE T STAT R CLASS 2 VOLTAGE TO THERMOSTAT G MANUAL FAN FROM T STAT C THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD TR CHASIS GROUND GRD Y1 THERMOSTAT 1ST STAGE COOL SIGNAL Y2 THERMOSTAT 2N...

Страница 7: ...2 100 50 OFF OPTION B OFF 82 100 OFF OPTION C OFF 100 100 OFF OPTION D OFF 100 OFF DEFAULT 10 10 HIGH SPEED MEDIUM HIGH SPEED MEDIUM LOW SPEED LOW SPEED 7 PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY B...

Страница 8: ...e flame signal mode The integrated control will display the flame current on 7 segment LED in in micro amps uA Flame signal mode is exited after any of the following D Power is reset D Pressing and ho...

Страница 9: ...clears 5 seconds after fault recovered E 111 Line voltage polarity reversed Reverse line power voltage wiring System resumes normal operation 5 seconds after fault recovered E 112 Ground not detected...

Страница 10: ...re will be set as installed and that could be seen in About screen In normal operation after control recognizes sensors alarm will be sent if valid temperature reading is lost To get rid of set ting a...

Страница 11: ...switch open during trial for ignition or run mode Refer to troubleshooting Check pressure inches w c of low pressure switch closing on heat call Measure operating pressure inches w c Inspect vent and...

Страница 12: ...soft lockout Clears when calibra tion has finished successfully E 290 Ignitor circuit fault Failed ignitor or triggering circuitry Measure resistance of hot surface ignitor Replace if open or not wit...

Страница 13: ...tegrated control with non communi cating outdoor unit Dual fuel module required for heat pump applica tion Configuration link R to O needs to be restored Re place link or hard wire Applicable in non c...

Страница 14: ...econd stage on delay when a single stage ther mostat is being used The switch is factory set in the OFF position which provides a 7 minute delay before second stage heat is initiated If the switch is...

Страница 15: ...uns at 82 for approximately 7 1 2 minutes If demand has not been satisfied after 7 1 2 minutes motor runs at 100 until demand is satisfied S Once demand is met motor ramps down to stop OFF OFF 82 CFM...

Страница 16: ...tage Heating Speed cfm Second Stage Heating Speed cfm 24 985 1100 18 950 1050 12 875 1000 6 850 935 Factory Default 800 890 6 750 840 12 700 790 18 680 740 COOLING 1 Cooling Speed DIP Switch Settings...

Страница 17: ...tage Heating Speed cfm Second Stage Heating Speed cfm 24 1245 1385 18 1180 1320 12 1130 1245 6 1045 1185 Factory Default 1095 1120 6 1020 1050 12 825 975 18 840 865 COOLING 1 Cooling Speed DIP Switch...

Страница 18: ...witch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1375 1530 18 1330 1450 12 1260 1390 6 1185 1315 Factory Default 1130 1235 6 1050 1165 12 980 1090 18 940 1020 COOLING 1 C...

Страница 19: ...ressure Range HEATING 1 Heating Speed DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1350 1485 18 1280 1420 12 1220 1345 6 1155 1270 Factory Default 1100 1200 6 10...

Страница 20: ...and 0 through 1 0 in w g Cooling External Static Pressure Range HEATING 1 Heating Speed DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1600 1785 18 1530 1685 12 1...

Страница 21: ...t be cut if two stage cooling will be used If the Y1 to Y2 link is not cut the outdoor unit will operate in second stage cool ing only TABLE 12 OPERATING SEQUENCE SL280UHNV Non Communicating Thermosta...

Страница 22: ...wing the room space to maintain a cooler room thermostat setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE only active on a Y1 thermostat demand Normal Opera tion 1 On On On...

Страница 23: ...S BEARING ROTOR The controller uses sensing devices to sense what position the rotor is in at any given time By sensing the position of the rotor and then switching the motor windings on and off in se...

Страница 24: ...t before attempt ing to service motor DANGER Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before at tempting to service motor Failure to wait may cause pe...

Страница 25: ...48 5 Pin Line Voltage Connector J49 4 Pin Control Connector J48 5 Pin J49 4 Pin FIGURE 9 BLOWER B3 HARNESS CONNECTORS MOTOR with INTEGRATED CONTROLLER SHAFT P49 4 Pin P48 5 Pin P48 5 Pin P49 4 Pin J48...

Страница 26: ...re the resistance between each of the three motor leads 3 pin plug and the unpainted part of the end shield If the winding resistance to ground is 100k ohms replace the motor and control module If the...

Страница 27: ...regu lator adjustment screw is located on the valve LPG change over kits are available from Lennox Kits include burner orifices and a gas valve 4 Thermal Switch S47 The auto reset switch is located on...

Страница 28: ...SL280UHNV HEATING COMPONENTS FIGURE 13 Air Gas Plenum Burner Gasket Orifice Housing Gas Valve Air Orifice Sensor Ignitor Gas Orifice Thermal Switch location Intake Air Screen Intake Air Elbow Coupling...

Страница 29: ...is correct then then there is a problem with the wiring between the jack plug and control If the reading is not correct the issue is the ignitor Meter set to ohms Test 3 Insert meter probes into the t...

Страница 30: ...the combustion air inducer is not operat ing or if the flue becomes obstructed On heat demand first or second stage the switch senses that the combustion air inducer is operating It closes a cir cuit...

Страница 31: ...nit 1 Set thermostat to lowest setting 2 Turn off all electrical power to unit if service is to be per formed 3 Remove access panel 4 Move switch on valve to OFF Do not force 5 Replace access panel Fa...

Страница 32: ...e to the manometer E Proper Gas Flow Approximate Furnace should operate at least 5 minutes before check ing gas flow Determine time in seconds for two revolu tions of gas through the meter Two revolut...

Страница 33: ...power and gas supply to the fur nace 2 Remove the air hose fitting from the brass fitting on the air inlet screen 3 Use a 5 16 nut driver to loosen the clamps on the gray coupling 4 Remove the air inl...

Страница 34: ...1 219 19X32 G Proper Combustion Furnace should operate a minimum 15 minutes with cor rect manifold pressure and gas flow rate before checking combustion Take combustion sample beyond the flue out let...

Страница 35: ...eplace air orifice Check signal Pressure Signal pressure within range Replace gas valve Check the following 1 Vent air intake pipe restriction 2 Plugged air inlet screen 3 Signal hoses to gas valve fo...

Страница 36: ...TEMPERATURE RISE Supply Duct Temperature ________ Return Duct Temperature _ _____ Temperature Rise ________ C External Static Pressure 1 Tap locations shown in figure 23 2 Punch a 1 4 diameter hole i...

Страница 37: ...air inducer and clean if neces sary 8 Evaluate the heat exchanger integrity by inspecting the heat exchanger per the AHRI heat exchanger inspec tion procedure This procedure can be viewed at www ahrin...

Страница 38: ...used by for eign matter Remove any blockage Figure 24 shows burner detail Replace gasket between burner plate and air fuel plenum then re install burner plate 10 To clean the combustion air inducer vi...

Страница 39: ...IGURE 24 Gas Valve Air Intake Assembly Air Fuel Plenum Air Fuel Plenum Burner Heat Exchanger Re install screws per the numbered sequence shown Gasket Gasket Gasket replace FIGURE 25 Remove 5 screws if...

Страница 40: ...at prove switch normally open contacts Once self check is complete and all safety switches are operational heat call can continue NOTE The ignition control thermostat selection DIP switch is factory s...

Страница 41: ...operation The indoor blower motor is switched to the low fire heating speed 8 When the thermostat demand for low fire first stage heat is satisfied the gas valve is de energized and the field selected...

Страница 42: ...r control and four wires between the outdoor unit and the fur nace air handler control When a thermostat cable with more than four wires is used the extra wires must be properly connected to avoid ele...

Страница 43: ...RSBus Rf W Gh Gs Cf HVAC EQUIP DEHUMIDIFIER CONTROL HVAC EQUIPMENT DH STANDARD 1 OR 2 STAGE AC OR HP UNIT 24V IN JUMPER COMMUNICATING ENABLED FURNACE COMMUNICATING ENABLED FURNACE THERMOSTAT CONVENTIO...

Страница 44: ...ON DO NOT CUT ANY ON BOARD LINKS S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915...

Страница 45: ...15 2 STAGE COMPR S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat with humidity control OFF CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM OR HARMONY S1 T STAT FU...

Страница 46: ...RD LINK W951 HEAT PUMP L7742U T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w dual fuel capa bilities Capable of...

Страница 47: ...NK W914 DEHUM OR HARMONY L7742U T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w dual fuel capa bilities Capable o...

Страница 48: ...od During that period press and hold push button for 5 seconds Integrated control will store code in memory and will automatically exit Program Unit Capacity Size Mode and reset If second period expir...

Страница 49: ...DS H S I OFF NO INDUCER OFF AFTER POST PURGE HARD LOCKOUT ERROR CODE FLASHES YES YES YES 1 2 1 LOW PRESSURE SWITCH OPENS 1 2 HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOC...

Страница 50: ...ZED ONLY FOR 1ST REQUEST FOR 2ND STAGE HEAT YES CALL FOR HEAT SATISFIED INDUCER SWITCHED TO HIGH SPEED SINGLE STAGE THERMOSTAT 2 STAGE THERMOSTAT NO INDUCER SWITCHED TO LOW SPEED 5 MINUTE DELAY ERROR...

Страница 51: ...L 2ND STAGE CALL FOR HEAT SATISFIED NO YES DE ENERGIZE 2ND STAGE GAS VALVE INDUCER SPEED SWITCHED TO LOW SPEED 1 2 3 1ST STAGE HEAT 1ST STAGE CALL FOR HEAT SATISFIED NO YES GAS VALVE DE ENERGIZED INDU...

Страница 52: ...SPEED RAMPING PROFILES THE SPECIFIC PROFILE IS SELECTED USING THE 1 1 2 2 1 1 1 2 2 DE ENERGIZE 1ST STAGE COOLING CONTACTOR COMPRESSOR FAN 2ND STAGE COOLING REQUEST STILL ACTIVE COOLING REQUEST STILL...

Страница 53: ...1ST STAGE HEAT YES GO TO CALL FOR COOLING 1 1 1 4 YES NO CALL FOR FAN INDOOR BLOWER ON CONTINUOUS FAN SPEED MAINTAIN INDOOR BLOWER AT CONTINUOUS FAN MAINTAIN INDOOR BLOWER AT CONTINUOUS FAN DE ENERGIZ...

Отзывы: