Page 8

Indoor Coil Placement

 When matching a Lennox branded A­coil to an upflow oil
furnace, make sure coil width is appropriate for full air flow
into and through the coil. If there is any doubt, it is recom­
mended that coil is installed at least four inches above the
furnace cabinet. If a non­Lennox coil is used, consult the
coil’s literature for the recommended distance from the top
of the furnace cabinet. If the literature does not have a re­
commended distance, the coil should be mounted  at least
eight inches above top of furnace cabinet

.

Venting

WARNING

Combustion air openings in front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may re­
sult in a fire hazard.

WARNING

The barometric draft control must be removed from
the vent pipe when using an air intake kit.  Deviation
from this practice will cause improper burner opera­
tion and may allow flue products into the living
space which may result in personal injury or death.

An air intake kit used to to provide fresh air directly to the
burner, is available through Lennox. Order part number
11F44.

Figure 9

Vacuum

Relief

Valve

Air Intake Kit

Air Intake Kit Installed

CAUTION

Do not store combustible materials near the furnace
or supply air ducts. The material (such as paint, mo­
tor oil, gasoline, paint thinner, etc.) may ignite by
spontaneous combustion creating a fire hazard.

WARNING

This furnace is certified for use with type “L” vent.
“B” vent must not be used with oil furnaces.

Prior to installation of unit, make a thorough inspection of the
chimney to determine whether repairs are necessary. Make
sure the chimney is properly constructed and sized ac­
cording to the requirements of the National Fire Protection
Association. The smallest dimensions of the chimney
should be at least equal to the diameter of the furnace vent
connector. Make sure the chimney will produce a steady
draft sufficient to remove all the products of combustion
from the furnace. A draft of at least .04” w.c. (9.9 Pa) is re­
quired during burner operation.

 1 - Local building codes may have more stringent instal­

lation requirements and should be consulted before
installation of unit.

 2 - The vent connector should be as short as possible to

do the job.

 3 - The vent connector should not be smaller than the

outlet diameter of the vent outlet of the furnace.

 4 - Pipe should be at least 24 gauge galvanized.

 5 - Single wall vent pipe sh+ould not run outside or

through any unconditioned space.

 6 - Chimney should extend 3 feet (0.9 m) above highest

point where the vent passes through the roof, and 2
feet (0.6 m) higher than any portion of a building within
a horizontal distance of 10 feet (3 m).

 7 - The vent must not pass through a floor or ceiling.

Clearances to single wall vent pipe should be no less
than 6” (152 mm); more if local codes require it.

 8 - The vent may pass through a wall where provisions

have been made for a thimble as specified in the Stan­
dards of the National Board of Fire Underwriters. See
figure 10.

Wall Thimble

Figure 10

Thimble

Vent Pipe

Combustible

Wall

 9 - The vent pipe should slope upward toward the chim­

ney on horizontal run at least 1/4 inch (6 mm) to the
foot (0.3 m) and should be supported by something
other than the furnace, such as isolation hangers.

Содержание SIGNATURE SLO185UFV Series

Страница 1: ...ng List 1 SLO185UFV Unit Dimensions 2 SLO185UFV Unit Parts Arrangement 3 SLO185UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Vent...

Страница 2: ...her Side ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D...

Страница 3: ...SPEED BLOWER MOTOR OBSERVATION PORT HEAT EXCHANGER FLUE COLLAR LIMIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO185UFV NX Burner Parts Arrangement Blower Motor Blower Wheel With Air Gu...

Страница 4: ...gs required SLO185UFV 79 105 10 X 20 254 mm X 508 mm SLO185UFV 124 141 11 X 22 279 mm X 559 mm This unit is approved for use on combustible flooring and for clearances to combustible material as liste...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking effect of louvers...

Страница 7: ...le assembly must be checked for proper depth and alignment You must remove the entire burner assembly not just the nozzle from the furnace to check the nozzle depth and alignment The smaller sized fir...

Страница 8: ...make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized ac cording to the requirements of the National Fire Protec...

Страница 9: ...nt connectors serving this appliance shall not be connected into any portion of mechanical draft sys tems operating under positive pressure 18 Keep the area around the vent terminal free of snow ice a...

Страница 10: ...aft control Alternate Side Flue Connections The vent pipe may exit the top or sides of the cabinet A hole is provided in the top cap for top exit For side exit lo cate the center hole punched in the s...

Страница 11: ...returning it to the tank To determine the run and lift for piping refer to table 5 Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe Install oil supply pipe under f...

Страница 12: ...he building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 6 lists the filters for the SLO185UFV furnace Table 6 Oil Filters Cat No 10 micron...

Страница 13: ...this product may result in a fire causing property dam age severe injury or death Use copper wire only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in...

Страница 14: ...Page 14 Figure 17 Field Wiring Diagrams 1 Heat 1 Cool 1 Heat 2 Cool 1 Heat 1 Cool With Thermostat Dehumidification Mode 1 Heat 2 Cool With Thermostat Dehumidification Mode...

Страница 15: ...iagrams Continued Dual Fuel Single Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode and T...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the motor between cycles This is normal operation After the CFM for each applica...

Страница 18: ...External Static Pressure Range ADJUST Jumper Setting Jumper Speed Positions HEAT Speed COOL Speed 85 High Fire 75 Low Fire A C A B C D cfm cfm cfm cfm cfm cfm N A N A 2000 2000 1800 NORM 1850 1550 20...

Страница 19: ...of bubbles Then terminate the call for heat The burner control will resume normal operation Fuel Pump Pressure Adjustment Measure fuel pump pressure with unit off Attach pressure gauge to pump outlet...

Страница 20: ...er obtain and record the flue gas temperature at the service hole 11 Use the CO2 reading and the flue gas temperature reading to determine unit efficiency 12 When proper combustion and smoke readings...

Страница 21: ...tube CAUTION Do not attempt to clean the combustion chamber It can be easily damaged 5 Replace the three clean out caps and flue access el bow Make sure locking screws are secure 6 Brush out and vacu...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...speed ramps down Circulating fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory co...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...must be removed from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle straine...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...ed heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High sta...