background image

Page 5

TYPICAL HEAT EXCHANGER ASSEMBLY

120, 240, & 288 UNITS

FIGURE 4

BURNER

COMBUSTION

AIR INDUCER

VENT

CONNECTOR

GAS VALVE

HEAT

EXCHANGER

TUBE

Service

To maintain efficiency and longevity, your equipment
must be serviced yearly by a qualified service technician.
Failure to provide proof of service can void warranty.

CAUTION

Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.

Servicing Filter

Units are equipped with the number of filters shown in
table 1. Filters should be checked monthly and replaced
when necessary with filters of like kind and size. Take note
of air flow direction marking on filter frame when
reinstalling filters. See figure 5.

REMOVE FILTERS

PULL TO REMOVE
FILTERS

FIGURE 5

NOTE−Filters must be U.L.C. certified or equivalent for
use in Canada.

TABLE 1

NUMBER AND SIZE OF FILTER BY UNIT

SG Unit

Qty Filter Size − inches (mm)

036, 060

4

16 X 20 X 2 (406 X 508 X 51)

120

6

16 X 25 X 2 (457 X 635 X 51)

240, 288

12

20 X 20 X 2 (508 X 508 X 51)

Lubrication

All motor bearings are prelubricated. No further
lubrication is required.

Blower shaft bearings are prelubricated. For extended
bearing life, relubricate at least once every two years
with a lithium base grease, such as Alvania 3 (Shell Oil),
Chevron BRB2 (Standard Oil) or Regal AFB2 (Texas
Oil). Use a hand grease gun for relubrication. Add only
enough grease to purge through the bearings so that a
bead of grease appears at the seal lip contacts.

Manifold Pressures

Manifold pressures are shown in table 2. Refer to figure 2
to locate pressure ports.

TABLE 2

MANIFOLD INPUT PRESSURES

 in.wg. (kPa)

SG Unit

Natural Gas

Propane (LP) Gas

1st Stage

+ 0.2

(+.05)

2nd Stage

+ 0.3

(+.08)

1st Stage

+ 0.2

(+.05)

2nd Stage

+ 0.3 
(+.08)

036

NA

3.7 (0.92)

NA

10.5 (2.61)

060,

120, 240,

288

1.6 (0.40)

3.7 (0.92)

5.5 (1.37)

10.5 (2.61)

Burners

Clean burners as follows:

 1− Turn off both electrical power and gas supply to unit.

 

2− Open or remove access panel to burner

compartment.

 3− On 036 and 060 units, remove and retain four screws

securing burner support cap and lift burners from
orifices. See figure 6. On 120, 240, and 288 units,
remove and retain two screws securing burners to
burner support. See figure 7.

 4− Clean as necessary and replace burners. On 036 and

060 units, replace burner support cap and secure
with retained screws. On 120, 240, and 288 units,
secure burners with retained screws. Replace burner
compartment access panel.

Содержание SGA036

Страница 1: ...or s phone Follow the gas suppli er s instructions D If you cannot reach your gas supplier call the fire department Dallas Texas D Extinguish any open flames ROOFTOP UNITS READ ALL INSTRUCTIONS IN THI...

Страница 2: ...20 X 2 ECONOMIZER DAMPERS OPTIONAL BURNERS FILTER DRIER L L E N O X N L E N O X N IMC SG 120 Parts Arrangement L E N O X N L E N O X N L E N O X N L E N O X N COMBUSTION AIR INDUCER EVAPORATOR COIL BL...

Страница 3: ...ustment alteration ser vice or maintenance can cause property damage personal injury or loss of life Installation and ser vice must be performed by a qualified installer ser vice agency or the gas sup...

Страница 4: ...operty Vent ini tial supply air outside when possible Unit Operation FOR YOUR SAFETY READ BEFORE LIGHTING BEFORE LIGHTING smell all around the furnace area for gas Be sure to smell next to the floor b...

Страница 5: ...gas supplier Turning Off Gas to Furnace 1 If using an electromechanical thermostat set to the lowest setting 2 Before performing any service turn off all electrical power to the furnace 3 Open or remo...

Страница 6: ...er lubrication is required Blower shaft bearings are prelubricated For extended bearing life relubricate at least once every two years with a lithium base grease such as Alvania 3 Shell Oil Chevron BR...

Страница 7: ...s obstructed Under normal operating conditions the combustion air blower wheel should be checked and cleaned prior to the heating season However it should be examined periodically during the heating s...

Страница 8: ...is required 1 Be sure electrical disconnect switches are ON 2 Check room thermostat for proper setting 3 Replace any blown fuses or reset circuit breakers 4 Gas valve should be ON 5 Air filters shoul...

Отзывы: