SGH/SCH036, 060, 120, 240

MSAV

t

 Unit Start-Up  

Units may contain a supply air blower equipped with a
variable frequency drive A96 (VFD) which stages supply air
CFM.

The supply air VFD (A96) is located near the compressors.
See figure 34.

FIGURE 34

SUPPLY AIR VARIABLE FREQUENCY DRIVE

SUPPLY AIR VFD (A96)

SC/SG 240 LOCATION

SUPPLY AIR VFD

(A96) SC/SG120

LOCATION

A-Design Specifications

Use table 24 to fill in field-provided, design specified blower
CFM for appropriate unit.

If only high and low cooling design specifications are
provided, set the medium cooling CFM at the high or low
cooling design spec or any CFM between.

B-Set Maximum CFM

Use table 24 to determine highest blower CFM for
appropriate unit. Adjust the blower pulley to deliver that
amount of CFM with only the blower operating. See

Determining Unit CFM

 in the Blower Operation and

Adjustment section.

C-Enter Design Specifications Into Controller

1- Use the following menu to enter the blower design

specified CFM into the Unit Controller. Make sure
blower CFM is within limitations shown in table 25.
Refer to the Unit Controller manual provided with unit.

SETUP>TEST & BALANCE>BLOWER> (enter information
as prompted by the Unit Controller if not already done).

2- Enter the following design specifications as shown in

table 30.

Blower / 

Heat CFM
Cooling High CFM

1

Cooling Low CFM

1

Vent CFM

1

The Unit Controller will prompt when more cooling stages

are available depending on the number of compressors and
the control mode.

3- Adjust the blower RPM to deliver the target CFM based

on the measured static pressure using the blower table.

4- Measure the static pressure again and apply the static

pressure and RPM to the tables to determine adjusted
CFM.

5- Repeat adjustments until design CFM is reached.

D-Set Damper Minimum Position

To maintain required minimum ventilation air volumes when

the unit is in the occupied mode, two minimum damper

positions must be set. The Unit Controller will open the

dampers to “Min OCP Blwr Low” when blower CFM is

BELOW a “midpoint” CFM. The Unit Controller will open the

damper to “Min OCP Blwr High” when blower CFM is at or

ABOVE the “midpoint” CFM.

The Unit Controller will calculate the “midpoint” CFM.

Set Minimum Position 1

Use the following menu in the Unit Controller to set “Min

OCP Blwr Low” for the blower CFM below the “midpoint”

CFM. When navigating into this menu, the Unit Controller

will bring on the corresponding blower speed and allow

damper position adjustment.

SETTINGS>RTU OPTIONS>DAMPER>

MIN DAMPER POSITION BLOWR ON HIGH = X.X%

TABLE 24

Blower CFM Design Specifications

Unit

T'Stat or

Zone Con­
trol Stages

Blower Speed

Design

Specified CFM

120, 
240

2

Htg.

Clg. High

Clg. Low

Ventilation

240

4

Htg.

Clg. High

Clg. Med. High

Clg. Med. Low

Clg. Low

Ventilation

*Available blower speeds vary by unit and thermostat
stages.

Содержание SCH036

Страница 1: ...43 MSAVt Unit Start Up Page 45 MSAVt Operation Page 46 Direct Drive Start Up Page 47 Hot Gas Reheat Startup Page 49 Economizer Start Up Page 53 Service Page 55 Factory Control Parameter Settings Page...

Страница 2: ...IEW LIFTING HOLES For Rigging Front and Back 81 2057 82 7 8 2105 28 7 8 733 5 1 4 133 72 1 4 1835 41 3 8 1050 3 1 2 89 37 7 8 962 1 1 2 38 GAS SUPPLY 115V OUTLET Factory Installed Inside Unit Field Wi...

Страница 3: ...FORKLIFT SLOTS 51 3 8 1305 47 7 8 1216 77 5 16 1964 86 7 16 2196 5 3 8 137 5 1 4 133 BOTTOM OUTDOOR AIR INTAKE CIRCUIT BREAKER COVER FLUE OUTLET CONDENSER FANS AND GUARDS 2 OUTDOOR AIR HOOD Factory In...

Страница 4: ...28 711 28 711 4 102 9 229 20 508 20 508 18 457 OUTDOOR AIR HOOD Factory Installed Option CONDENSATE DRAIN 5 3 8 137 3 1 4 83 GAS SUPPLY CIRCUIT BREAKER COVER 115V OUTLET Factory Installed Inside Unit...

Страница 5: ...OWER CONDENSATE DRAIN FILTERS FOUR 16 X 20 X 2 ECONOMIZER DAMPERS OPTIONAL BURNERS FILTER DRIER UNIT CONTROLLER REHEAT COIL SC 036 060 Parts Arrangement EVAPORATOR COIL CONDENSER FANS CONDENSER COIL C...

Страница 6: ...FILTER DRIERS SUPPLY AIR VFD CONDENSER AIR INTAKE THROUGH UNIT BASE COMBUSTION AIR INDUCER BURNERS GAS VALVE REHEAT COIL SC 120 Parts Arrangement BLOWER MOTOR CONDENSER FANS 2 CONDENSER COILS COMPRESS...

Страница 7: ...NDENSATE DRAIN FILTERS TWELVE 20 X 20 X 2 ECONOMIZER DAMPERS OPTIONAL UNIT CONTROLLER SUPPLY AIR VFD FILTER DRIERS REHEAT COIL SC 240 Parts Arrangement BLOWER MOTOR FILTERS TWELVE 20 X 20 X 2 ELECTRIC...

Страница 8: ...th a total of 10 ton cooling capacities The SG 240 gas electric packaged rooftop unit is available in 260 000 360 000 or 480 000 Btuh heating inputs The SC 240 cooling packaged rooftop unit is the sam...

Страница 9: ...ctions NOTE The Commonwealth of Massachusetts stipulates these additional requirements S Gas units shall be installed by a licensed plumber or gas fitter only S The gas cock must be T handle type Unit...

Страница 10: ...holes in unit base rail See figure 3 1 Detach wooden base protection before rigging 2 Connect rigging to the unit base using both holes in each corner 3 All panels must be in place for rigging 4 Place...

Страница 11: ...ve See figure 5 or 6 for gas supply piping entering outside the unit See figure 7 for gas supply piping entering bottom the unit Compounds used on threaded joints of gas piping shall be resistant to t...

Страница 12: ...gas leaks WARNING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re sult in serious injury death or property damage Never test for gas leaks with an open flame Use a comm...

Страница 13: ...rd Screen Option Outdoor air hood is shipped folded down over the horizontal supply air opening Install hood as follows 1 Remove left side from hood top panel See figure 10 2 Remove and retain screws...

Страница 14: ...end of air hood 6 Install back filter bracket on unit division panel as shown in figure 14 7 Secure side seals to the hood sides as shown in figure 15 8 Install longer front filter bracket on hood to...

Страница 15: ...dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys B Control Wiring The Unit Controller will operate the unit from a the...

Страница 16: ...ring connections as shown in figure 16 for Thermostat Mode or figure 17 for Zone Sensor Mode In addition connect either a humidity sensor or a dehumidification input See figure 18 or 19 for humidity s...

Страница 17: ...ower Operation Note On units with staged blowers use the Unit Controller to start the blower Refer to the appropriate start up section Initiate blower demand at thermostat according to instructions pr...

Страница 18: ...WS TO SLIDE BLOWER ASSEMBLY OUT OF UNIT BELT TENSION ADJUSTING BOLT TURN CLOCKWISE TO TIGHTEN TO INCREASE BELT TENSION 1 Loosen front and back screws securing pivoting motor base to slotted arm 2 Turn...

Страница 19: ...OSEN FOUR SCREWS TO AD JUST BELT TENSION BLOWER MOTOR REMOVE SCREWS TO SLIDE BLOWER ASSEMBLY OUT OF UNIT LOOSEN SCREWS TO ADJUST BELT TENSION PULLEY ALLEN SCREW BELT TENSION ADJUSTING SCREWS BLOWER AS...

Страница 20: ...n in table 2 TABLE 2 Minimum and Maximum Pulley Adjustment Belt Minimum Turns Open Maximum Turns Open A Section 0 5 B Section 1 6 No minimum number of turns open when B belt is used on pulleys 6 O D o...

Страница 21: ...33 2158 460 2202 486 2244 513 2285 542 2327 573 1400 1819 273 1873 299 1926 324 1977 350 2027 377 2075 404 2122 431 2168 459 2212 486 2255 515 2297 543 2338 572 2378 602 2419 635 1500 1935 318 1987 34...

Страница 22: ...525 0 72 569 0 83 613 0 93 653 1 02 689 1 11 724 1 20 758 1 31 793 1 44 829 1 58 864 1 72 897 1 85 928 1 97 956 2 08 3200 547 0 84 591 0 95 634 1 05 672 1 14 707 1 23 741 1 34 776 1 47 812 1 61 848 1...

Страница 23: ...686 2 50 722 2 70 759 2 89 796 3 08 5400 346 0 92 400 1 12 444 1 33 484 1 51 522 1 67 556 1 86 589 2 04 622 2 23 655 2 41 690 2 60 727 2 79 764 2 98 801 3 17 5600 355 0 96 407 1 17 450 1 40 490 1 58 5...

Страница 24: ...2234 524 2282 554 2329 586 1400 1738 266 1803 293 1865 320 1923 347 1979 373 2031 401 2082 428 2131 456 2179 485 2227 514 2274 545 2320 575 2366 607 2411 641 1500 1855 305 1915 333 1973 361 2028 389...

Страница 25: ...1 33 813 1 43 843 1 52 872 1 60 902 1 69 3000 489 0 74 525 0 81 564 0 89 607 0 97 649 1 06 688 1 16 725 1 27 761 1 38 795 1 48 826 1 58 857 1 66 887 1 75 918 1 84 3200 506 0 86 543 0 93 583 1 01 625...

Страница 26: ...1 59 551 1 77 585 1 95 617 2 13 651 2 32 686 2 50 722 2 70 759 2 89 796 3 08 5400 346 0 92 400 1 12 444 1 33 484 1 51 522 1 67 556 1 86 589 2 04 622 2 23 655 2 41 690 2 60 727 2 79 764 2 98 801 3 17 5...

Страница 27: ...LED OPTIONS FIELD INSTALLED ACCESSORY AIR RESISTANCE in w g Air Volume cfm Dehumidification Coil Economizer Filters MERV 13 036 060 MODELS 800 0 00 0 04 0 05 1000 0 00 0 04 0 07 1200 0 01 0 04 0 07 14...

Страница 28: ...5 75 4 staged 5 staged 520 685 685 865 7 5 8 63 7 staged 770 965 TABLE 13 SG SC 120 Manufacturer s Numbers Drive No DRIVE COMPONENTS ADJUSTABLE SHEAVE FIXED SHEAVE BELTS Supplier No OEM Part No Suppli...

Страница 29: ...thermostat demand will energize compressor 2 On units with an economizer when outdoor air is acceptable a first stage demand will energize the economizer a second stage demand will energize compresso...

Страница 30: ...ANT Mineral oils are not compatible with R410A If oil must be added it must be a polyol ester oil CIRCUIT 1 CONDENSER COIL FIGURE 27 SG SC 120 MSAVt UNIT REFRIGERANT CIRCUITS 2 CIRCUIT 2 CONDENSER COI...

Страница 31: ...rant to the system D If measured liquid temperature is lower than the target liquid temperature recover some refrigerant from the system 5 Add or remove charge in increments Allow the system to stabil...

Страница 32: ...21 403 124 457 118 244 120 280 122 321 126 364 129 411 132 465 136 252 140 286 142 326 144 375 147 428 150 483 152 278 157 303 162 338 166 381 169 430 172 486 Circuit 2 110 250 112 286 116 329 117 374...

Страница 33: ...17 419 119 487 117 245 119 280 120 326 123 373 126 428 129 484 135 253 137 286 140 329 142 375 146 432 149 494 151 267 157 296 162 340 165 382 168 434 172 497 Circuit 3 104 236 104 273 107 323 109 371...

Страница 34: ...0 100 110 120 SG SC 036 Charging Curves Reheat 580979 01 Outdoor Temperature F 110 120 130 140 150 160 170 180 Suction Pressure psig 115 105 95 85 75 65 60 70 80 90 100 110 120 110 120 130 140 150 160...

Страница 35: ...Page 35 SGH SCH036 060 120 240 Suction Pressure psig 115 105 95 85 75 65 60 70 80 90 100 110 120 SG SC 060 Charging Curves Reheat 580980 01 Outdoor Temperature F 110 120 130 140 150 160 170 100...

Страница 36: ...Temperature F 115 105 95 85 75 65 Circuit 1 SG SC 120 Reheat No Reheat 580740 02 110 120 130 140 150 160 170 100 60 70 80 90 100 110 120 130 Suction Pressure psig Outdoor Temperature F 115 105 95 85 7...

Страница 37: ...115 105 95 85 75 65 60 70 80 90 100 110 120 100 110 120 130 140 150 160 Circuit 1 SG SC 240 No Reheat 580974 01 170 Suction Pressure psig 115 105 95 85 75 65 Circuit 2 SG SC 240 No Reheat 580974 01 Ou...

Страница 38: ...80 90 100 110 120 Circuit 3 SG SC 240 No Reheat 580974 01 Outdoor Temperature F 100 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 115 105 95 85 75 65 70 80 90 100 110 120 11...

Страница 39: ...60 70 80 90 100 110 120 100 110 120 130 140 150 160 Circuit 1 SG SC 240 Reheat 580976 01 Outdoor Temperature F 170 Suction Pressure psig 115 105 95 85 75 65 Circuit 2 SG SC 240 Reheat 580976 01 Outdo...

Страница 40: ...70 80 90 100 110 120 Circuit 3 SG SC 240 Reheat 580976 01 Outdoor Temperature F 100 110 120 130 140 150 160 170 Suction Pressure psig 115 105 95 85 75 65 70 80 90 100 110 120 110 120 130 140 150 160...

Страница 41: ...ompressor 3 4 Controller respectively Condenser fan 3 is de energized when BOTH S11 and S84 open due to low pressure Condenser fan 4 is de energized when BOTH S85 and S94 open due to low pressure 4 Fr...

Страница 42: ...OFF Do not force 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not...

Страница 43: ...to HEAT position Primary Limit Location Limit controls are factory set and are not adjustable SG 036 060 On the vestibule to the right of the combustion air inducer See figure 32 SG 120 Upper right co...

Страница 44: ...nd restriction 3 Remove temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter TABLE 23 GAS METER CLOCKING CHART Unit Input Rate Btuh Sec...

Страница 45: ...M Cooling High CFM1 Cooling Low CFM1 Vent CFM 1The Unit Controller will prompt when more cooling stages are available depending on the number of compressors and the control mode 3 Adjust the blower RP...

Страница 46: ...the blower CFM above the midpoint CFM When navigating into this menu the Unit Controller will bring on the corresponding blower speed and allow damper position adjustment Settings Control MSAV Damper...

Страница 47: ...ake sure blower CFM is within limitations shown in table 27 Refer to the Unit Controller manual provided with unit SETUP TEST BALANCE BLOWER 3 Once all four speeds are entered the target highest of th...

Страница 48: ...POSITION BLOWER ON HIGH X X Measure the intake air CFM If the CFM is lower than the design specified CFM for ventilation air use the Unit Controller to increase the damper percent open If the CFM is...

Страница 49: ...ndoor relative humidity rises above 60 default The reheat setpoint can be adjusted by changing Unit Controller Settings Control menu A setting of 100 will operate reheat from an energy management syst...

Страница 50: ...IR REHEAT MODE REFRIGERANT ROUTING 240 FIGURE 37 REHEAT COIL REHEAT COIL EVAPORATOR COIL DEHUMIDIFIED NEUTRAL AIR MIXED INDOOR OUTDOOR AIR CONDENSER COIL NOTE Refrigerant circuits one and two operates...

Страница 51: ...Compressor 2 Cooling Blower High Speed Reheat Y1 Y2 Compressor 1 Cooling Compressor 2 Cooling Blower High Speed If there is no reheat demand and outdoor air is suitable free cooling will operate If t...

Страница 52: ...1 Reheat Compressor 2 3 4 Cooling3 Reheat Y1 Y2 Y3 Y4 Compressor 1 2 3 4 Cooling5 Cooling stage is initiated when zone temperature is higher than the cooling setpoint plus the appropriate stage differ...

Страница 53: ...is suitable Param eter M Motorized Out door Air Dampers None Dampers do not modulate dampers will open to minimum position during the occupied time period and close during the unoccupied time period...

Страница 54: ...dampers further or to keep them open The IAQ function is not energized during the unoccupied or night time period TABLE 32 ECONOMIZER OPERATION Standard Two Stage Thermostat Default Option THERMOSTAT...

Страница 55: ...ent for use in Canada TABLE 35 Number and Size of Filter By Unit SG SC Unit Qty Filter Size inches mm 036 060 4 16 X 20 X 2 406 X 508 X 51 120 4 20 X 25 X 2 508 X 635 X 51 240 12 20 X 20 X 2 508 X 508...

Страница 56: ...000 BTUH 5 BURNERS SENSOR IGNITOR SENSOR IGNITOR 70 000 BTUH 3 BURNERS SENSOR IGNITOR D Combustion Air Inducer SG Units A combustion air proving switch checks combustion air inducer operation before a...

Страница 57: ...off any dust from housing Clean accumulated dust from front of flue box cover 5 Return combustion air blower motor and vent connector to original location and secure with retained screws It is recomme...

Страница 58: ...rovided with each unit Tables 37 through 42 show factory settings in degrees of fan CFM etc Record adjusted settings on the parameter label located inside the compressor access panel TABLE 37 580902 0...

Страница 59: ...er exhaust operation TABLE 42 580904 01 SG SC 240 Staged Blower Parameter Factory Setting Field Setting Description 240 Note Any changes to Smoke CFM setting must be adjusted before the other CFM sett...

Страница 60: ..._________ Cooling Checks Compressor Rotation j Ambient Temp ________Return Air Temp ________ Supply Air Temp ________ Compressor Amps Compressor Volts Pressures Condenser Fan Amps CC Heater Amps L1 L2...

Отзывы: