IOM – FLEXY II – 1007 – E
Page 93
ELECTRICAL HEATER
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
Low airf low rate
Measure and estimate the airflow and pressure
and compare with the specification from
customer.
High Temperature trip
out on electric heater
Incorrect position of the Klixon
Check that the Klixon, is positioned in the airf low,
relocate Klixon if necessary
Check that there is no heat transf er f rom the
Klixon support.
WATER LEAKS
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
Cooling mode:
Water carried away f rom the coil because of
excessiv e airf low and speed on the coil.
Estimate the airflow rate and check the speed is
lower than 2.8 m/s
Low air pressure in the compartment due to a
high airf low rate or a high pressure drop before
the f an
Check f ilter
Reduce airflow rate
Water found in the
v entilation section
Check seals around the v entilation section.
Check the door seal
Check f or the presence of silicone seals in the
corners of the door and at the bottom of the
ref rigeration section bulkhead.
Water ingress in the
f ilter compartment
Water ingress through a leaking fresh air hood or
when running 100% f resh air
Check the seals and f langes in the f resh air hood
Reduce the airflow rate if necessary
DC50 & DS50
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
DC50: Nothing is
written on the screen
but it’s enlightened
Problem of addressing pLAN on the DC50
Press on the three right-hand side’s buttons at
the same time during a f ew seconds then
reconf igure the terminal address
(Conf er DC addressing procedure)
DS50: Nothing is
written on the screen
but it’s enlightened
Idem
Press on the three right-hand side’s buttons at
the same time during a f ew seconds then
reconf igure display address setting at 32.
Nothing occurs on the
unit or an option
disappeared
Possible problem of units' conf iguration
Check the instructions f rom 3811 to 3833 and
reconf igure options if necessary.
DS50 & DC50: the
message “No Link”
appears
Problem of addresses’ recognition
Disconnect the DS50 f rom the unit and then
reconnect it.
All the units are extinct
Problem BM50 pLAN addressing
Disconnect then re-plug; disconnect each unit
from the others then change all the pLAN
addresses
MAINTENANCE DIAGNOSTIC
Содержание ROOFTOP FLEXY FXK 100
Страница 1: ...Providing indoor climate comfort FLEXY II FLEXYII IOM 1007 E Installation operating and maintenance...
Страница 2: ......
Страница 11: ...IOM FLEXY II 1007 E Page 9 COMMENTS COMMISSIONING REPORT...
Страница 41: ...IOM FLEXY II 1007 E Page 39 VENTILATION AIRFLOW BALANCING AT18 18S...
Страница 42: ...IOM FLEXY II 1007 E Page 40 VENTILATION AIRFLOW BALANCING ADH355L...
Страница 43: ...IOM FLEXY II 1007 E Page 41 VENTILATION AIRFLOW BALANCING ADH450L...
Страница 44: ...IOM FLEXY II 1007 E Page 42 VENTILATION AIRFLOW BALANCING ADH500L...
Страница 60: ...IOM FLEXY II 1007 E Page 58 60kW 120kW HEATING GAS BURNER...
Страница 61: ...IOM FLEXY II 1007 E Page 59 180kW 240kW HEATING GAS BURNER...
Страница 68: ...IOM FLEXY II 1007 E Page 66 60kW 120kW HEATING MODULATING GAS BURNER...
Страница 69: ...IOM FLEXY II 1007 E Page 67 180kW 240kW HEATING MODULATING GAS BURNER...
Страница 73: ...IOM FLEXY II 1007 E Page 71 MAIN CURRENT DIAGRAM TRI 400V 50Hz T ELECTRICAL DATA WIRING DIAGRAMS...
Страница 74: ...IOM FLEXY II 1007 E Page 72 CLIMATIC 50 CONTROLER ELECTRICAL DATA WIRING DIAGRAMS...
Страница 75: ...IOM FLEXY II 1007 E Page 73 CLIMATIC 50 INPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Страница 76: ...IOM FLEXY II 1007 E Page 74 CLIMATIC 50 OUTPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Страница 77: ...IOM FLEXY II 1007 E Page 75 DAD SMOKE DETECTOR ELECTRICAL DATA WIRING DIAGRAMS...
Страница 78: ...IOM FLEXY II 1007 E Page 76 GENERAL CUSTOMER CONNECTION TCB ELECTRICAL DATA WIRING DIAGRAMS...
Страница 81: ...IOM FLEXY II 1007 E Page 79 WIRING DIAGRAM GAS BURNER 120kW ELECTRICAL DATA WIRING DIAGRAMS...
Страница 82: ...IOM FLEXY II 1007 E Page 80 WIRING DIAGRAM GAS BURNER 180 240kW ELECTRICAL DATA WIRING DIAGRAMS...
Страница 83: ...IOM FLEXY II 1007 E Page 81 WIRING DIAGRAM ELECTRIC HEATER ELECTRICAL DATA WIRING DIAGRAMS...
Страница 84: ...IOM FLEXY II 1007 E Page 82 GENERAL CUSTOMER CONNECTION DIAGRAM ELECTRICAL DATA WIRING DIAGRAMS...
Страница 89: ...IOM FLEXY II 1007 E Page 87 FCM 150 FHM 150 PRINCIPLE SKETCHES...
Страница 90: ...IOM FLEXY II 1007 E Page 88 FCM 170 FHM 170 PRINCIPLE SKETCHES...
Страница 91: ...IOM FLEXY II 1007 E Page 89 FCM 200 230 FHM 200 230 PRINCIPLE SKETCHES...
Страница 100: ...IOM FLEXY II 1007 E Page 98 LONGVIC SITE ISO 9001 2000 CERTIFICATE...
Страница 101: ...IOM FLEXY II 1007 E Page 99 EC CONFORMITY DECLARATION...
Страница 102: ...IOM FLEXY II 1007 E Page 100 DAD LOTUS CERTIFICATE...
Страница 103: ...IOM FLEXY II 1007 E Page 101 GLASS WOOL INSULATION CERTIFICATE...
Страница 104: ...IOM FLEXY II 1007 E Page 102 GLASS WOOL INSULATION CERTIFICATE...
Страница 105: ...IOM FLEXY II 1007 E Page 103 F7 FILTER INSULATION CERTIFICATE...
Страница 106: ...IOM FLEXY II 1007 E Page 104 G4 FILTER INSULATION CERTIFICATE...
Страница 107: ...IOM FLEXY II 1007 E Page 105 FLEXY 60 120 180 240 KW GAS BURNER CERTIFICATE...
Страница 108: ...IOM FLEXY II 1007 E Page 106 ROOFTOP PED CONFORMITY CERTIFICATE...
Страница 109: ...IOM FLEXY II 1007 E Page 107 ROOFTOP PED CONFORMITY CERTIFICATE...