background image

16

Service Information

Indoor Unit Alert Codes and Outdoor Unit LED

The following codes are display on the indoor unit LED on 

the outdoor unit.

Table 9.  Indoor Display Alert and Status Codes and 

Outdoor Unit LED

Unit Error Codes

Outdoor Unit 

Main Control 

Board

Indoor 

Unit 

Display

System Error Codes

Indoor unit EEPROM error

n/a

EH 00

Indoor unit EEPROM parameter error 

n/a

EH 0A

Communication error between indoor 

unit and outdoor units

n/a

EL 01

Indoor fan speed error (DC motor)

n/a

EH 03

Indoor room temperature sensor 

error (T1)

n/a

EH 60

Indoor coil temperature sensor error 

(T2)

n/a

EH 61

Refrigerant leakage detection 

(Cooling mode only)

n/a

EL 0C

Outdoor current overload protection

n/a

PC 08

Outdoor ambient temperature sensor 

error (T4)

n/a

EC 53

Outdoor coil temperature sensor 

error (T3)

n/a

EC 52

Compressor discharge temperature 

sensor error (T5)

n/a

EC 54

Outdoor unit EEPROM error

n/a

EC 51

Outdoor unit fan speed error (DC fan 

motor)

n/a

EC 07

Inverter module IPM error

n/a

PC 00

High or Low voltage protection

n/a

PC 01

Outdoor low ambient temperature 

protection 

n/a

PC 0L

Compressor drive error

n/a

PC 04

Standby

SLOW FLASH

n/a

Normal operation

LIT

n/a

Outdoor unit error

FAST FLASH

n/a

Communication error between main 

control board and display board

n/a

EH 0b

Operational Status Codes

46F heat mode

n/a

FP

Force Cooling

n/a

FC

Remote or Wired controller Lock 

n/a

LL

Defrost

n/a

dF

Active clean

n/a

CL

Time On

n/a

On

Time Off

n/a

OF

Anti­cold Air Flow

n/a

cF

Remote On/Off

n/a

CP

ECO mode

n/a

On display 

3 seconds

Outdoor Unit LED:
Slow flash: Flashing at 1Hz
Fast flash: Flashing at 2Hz

Test Run

Pre-Checks

Only  perform  test  run  after  you  have  completed  the 

following steps:

• 

Electrical  Safety  Checks  –  Confirm  that  the  unit’s 

electrical system is safe and operating properly.

• 

Refrigerant Leak Checks – Check all flare nut connec

­

tions and confirm that the system is not leaking.

• 

Confirm that suction and liquid valves are fully open.

Procedure

You should perform the Test Run for at least 30 minutes.

1.  Connect power to the unit.
2. 

Press the ON/OFF button on the remote controller to 

turn it on.

3.  Let each function run for 5 minutes, and perform the 

following checks:

Table 10. Test Run Checklist

Checks

Pass

Fail

No electrical leakage

Unit is properly grounded

All electrical terminals properly 

covered
Indoor and outdoor units are solidly 

installed
All pipe connection points do not leak

Water drains properly from drain hose

All piping is properly insulated

Unit performs COOL function properly

Indoor unit louvers rotate properly
Indoor unit responds to wireless 

remote

Double-Check Line Set Connections

During operation, the pressure of the refrigerant circuit 

will increase. This may reveal leaks that were not present 

during your initial leak check. Take time during the Test 

Run to double­check refrigerant line set  connections and 

verify there are no leaks. 

1. 

Using the wireless remote control, return unit to the 

normal operating temperature.

2. 

Using insulation tape, wrap the indoor refrigerant pipe 

connections that you left uncovered during the indoor 

unit installation process.

Содержание MWHB Series

Страница 1: ...indoor wall unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHB and M...

Страница 2: ...ing of refrigerant CFCs HCFCs and HFCs as of July 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may be levied for non compliance CAUTION As with...

Страница 3: ...n 012 1 ton 018 1 5 tons 024 2 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision M H B 009 S 4 S 1 P Series Type M Mini Split OUTDOOR SINGLE ZONE HEAT PUMP UNITS Cooling Efficiency...

Страница 4: ...14 11 1 4 286 30 7 8 784 21 7 8 556 17 3 4 451 30 1 8 765 2 3 4 70 2 3 8 60 3 5 8 92 11 7 8 302 Figure 2 9K and 12K Outdoor Unit Dimensions Inches mm DRAIN HOLE bottom of unit FRONT VIEW SIDE VIEW TOP...

Страница 5: ...mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K Left rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K 1 7 8 48 18K 2 1 8 54 24K...

Страница 6: ...Rc Rockwell scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs 12 N m for small valves to 25 ft lbs 34 N for large valves to prevent...

Страница 7: ...se a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate to the wall using the provided screws and screw anchors NOTE It is imp...

Страница 8: ...r unit 3 Drain should be as short as possible and should not have any droops or kinks that would restrict condensate flow and shall be approved resistant pipe There must be a 2 inch 51 mm space betwee...

Страница 9: ...ne security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation...

Страница 10: ...earing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof Damage This system contains both refrigerant and oil Some rubber roofing...

Страница 11: ...nto the refrigerant piping before it is connected 10 CAREFULLY adjust refrigerant piping connections to suit the application 11 Slowly loosen one of the flare nuts to release the factory nitrogen char...

Страница 12: ...sible and must be insulated to prevent condensation OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT INDOOR UNIT Maximum Line Set Length Maximum Line Set Length Maximum Elevation Outdooor Unit BELOW Indoor Unit...

Страница 13: ...port connections liquid and gas line pipes until a positive pressure is achieved 3 Evacuate the system to a reading of 5000 Microns 5 Torr 4 Break the vacuum by allowing nitrogen into the port connec...

Страница 14: ...ingle Zone Wiring IMPORTANT This unit must be properly grounded and protected by a circuit breaker The ground wire for the unit must not be connected to a gas or water pipe a lightning conductor or a...

Страница 15: ...line service valves to release the refrigerant charge contained in outdoor unit into the system 5 Replace the stem caps and tighten to the value listed in Table 1 Torque Requirements on page 6 6 Check...

Страница 16: ...Anti cold Air Flow n a cF Remote On Off n a CP ECO mode n a On display 3 seconds Outdoor Unit LED Slow flash Flashing at 1Hz Fast flash Flashing at 2Hz Test Run Pre Checks Only perform test run after...

Страница 17: ...is below 60 F 16 C In this instance you can use the MANUAL CONTROL button on the indoor unit to test the COOL function 1 Lift the front panel of the indoor unit and raise it until it clicks in place 2...

Страница 18: ...18 Indoor Unit Wiring Diagrams Figure 34 MWHB 09K 12K and 18K 115V and 208 230VAC Indoor Unit Wiring Diagram 16022000C27182 Figure 35 MWHB 24K 208 230VAC Indoor Unit Wiring Diagram...

Страница 19: ...19 Outdoor Unit Wiring Diagrams Figure 36 MHB 9K and 12K 115VAC Outdoor Unit Wiring Diagram Figure 37 09K 12K and 18K 208 230VAC Outdoor Unit Wiring Diagram...

Страница 20: ...20 Figure 38 MHB 24K 208 230VAC Outdoor Unit Wiring Diagram...

Отзывы: